We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Danfoss 131N0214 VLT HVAC Drive FC-101 55kW Three Phase 380 - 480 VAC IP54
MPN: 131N0214
Alt. SKU: FC-101P55KT4E5AH3XAXXXXSXXXXAXBXCXXXXDX
Why Choose the Danfoss FC‑101 HVAC Basic Drive (Part 131N0214)?
The Danfoss FC‑101 (P55K), part number 131N0214, offers powerful 55 kW (75 HP) three-phase motor control for HVAC, pump, and compressor systems. It operates on 380–480 VAC and is housed in an IP54 enclosure (Frame I7; not Type 12). This variant features a built‑in **RFI filter Class A1/B (IEC C1)**, an alpha‑numeric Local Control Panel (LCP), and comes with an uncoated PCB. It ships with no brake chopper, mains option, or optional software/hardware enhancements.
Technical Specifications
| Part Number | 131N0214 |
|---|---|
| Model Code | FC‑101P55KT4E5AH3XAXXXXSXXXXAXBXCXXXXDX |
| Power Rating | 55 kW / 75 HP |
| Voltage | 380–480 VAC, three‑phase |
| Enclosure | IP54 chassis (Frame I7; not Type 12) |
| RFI Filter | Class A1/B (IEC C1) |
| Brake Chopper | Not included |
| Local Control Panel (LCP) | Included — alpha‑numeric interface |
| PCB Coating | Not coated |
| Net Weight | ≈ 42.2 kg |
| Gross Weight | ≈ 44.6 kg |
| Frame Size | I7 |
| Certifications | CE, UL/cUL, RoHS; UL LZGH2 compliant (supports A2L refrigerants) |
Frequently Asked Questions
- How much energy can this drive save?
- Which EMC/RFI class does it meet?
- Which motor types are supported?
- Can it integrate with building management systems?
Typical Applications
- HVAC panels for fans, pumps, and compressors
- Commercial HVAC, chilled water, booster, and refrigeration systems
- OEM or retrofit installations requiring IP54-level protection and onboard control interface
Key Features
- 55 kW / 75 HP output @ 380–480 VAC
- IP54 IP-rated enclosure (Frame I7) for damp or dusty environments
- Built‑in Class A1/B (IEC C1) RFI filter with DC choke—external filtering not usually needed for ≤ 20 m motor cable
- Alpha‑numeric LCP included for commissioning and diagnostics
- Supports both induction and permanent‑magnet motors via EC+ optimized V/f and sensorless vector control
- Embedded communication support: BACnet MS/TP, Modbus RTU, N2, and LonWorks via RS‑485
- Automatic Energy Optimizer delivers ~3–5 % energy savings from startup, contributing to up to 50 % system-level reductions
- Includes Fire Mode (Safe Torque Off), Flying Start, and auto‑restart functionality
| Manufacturer Part Number | 131N0214 |
|---|---|
| Barcode | 5702427810853 |
| Height | 680mm |
| Width | 308mm |
| Depth | 310mm |
| Brake - Safe-Stop | No brake chopper |
| Coating PCB | Not coated PCB |
| Control Panel | Alpha Numeric LCP |
| Filter | (H3) RFI Class A1/B (C1) |
| Input Phases | Three Phase |
| Degree of protection (IP) | IP54 |
| KW Rating | 55kW |
| Output Phases | Three phase |
| VSD Range | Danfoss VLT HVAC Drive FC-101 |
| Manufacturer | Danfoss |
| Alternative Product SKU | FC-101P55KT4E5AH3XAXXXXSXXXXAXBXCXXXXDX |