We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
ABB s201m-d2 mcb s200m 1 pole d type 2amp
MPN: 2CDS271001R0021
Alt. SKU: S201M-D2
Why Choose the S201M-D2 [2CDS271001R0021]
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Technical Specification
- Function: Miniature circuit breaker with thermal and electromechanical tripping for overload and short circuit protection.
- Rated Voltage: Up to 400 V AC (230/400 V AC typical).
- Rated Current: Up to 63 A; this model rated for 2 A.
- Contact Configuration: 1 Pole (1P).
- Breaking Capacity: Ultimate up to 25 kA at 133 V AC, 15 kA at 230/400 V AC; Service up to 18.8 kA at 133 V AC, 7.5 kA at 230 V AC.
- Terminal Type & Capacity: Screw terminals, bi-directional cylinder-lift; supports flexible cables 0.75–25 mm² and rigid cables up to 35 mm².
- Electrical Endurance: 20,000 AC cycles.
- Mechanical Endurance: 20,000 cycles.
- Insulation & Dielectric Strength: Dielectric test voltage 2 kV at 50/60 Hz for 1 minute.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the function of the S200M miniature circuit breaker?
What are the available configurations for the S200M?
What is the maximum breaking capacity of the S200M?
What is the rated current for the S200M model?
What types of cables can be used with the S200M?
What is the electrical endurance of the S200M?
Does the S200M comply with any standards?
| Manufacturer Part Number | 2CDS271001R0021 |
|---|---|
| Amperage | 2A |
| Number of Poles | 1 Pole |
| Trip Curve Type | Type B 10KA |
| Manufacturer | ABB |
| Alternative Product SKU | S201M-D2 |
| Barcode | 4016779599337 |