Why Choose the S202M-D1 [2CDS272001R0011]

System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.

Technical Specification

  • Function: Two tripping mechanisms - delayed thermal for overload and electromechanic for short circuit protection.
  • Voltage Ratings: Rated ultimate short-circuit breaking capacity up to 25 kA at 230 V AC and 15 kA at 400/440 V AC.
  • Current Rating: Rated current up to 63 A.
  • Contact Configuration: 2 poles (2P) with red ON / green OFF position indication.
  • Terminal Type and Size Range: Screw terminals accepting busbar 10/10 mm², flexible cables 0.75–25 mm², and rigid cables 0.75–35 mm².
  • Mechanical and Electrical Endurance: 20,000 AC cycles mechanical and electrical endurance.
  • Insulation and Dielectric Strength: Dielectric test voltage 2 kV at 50/60 Hz for 1 minute.
  • Actuator: Toggle type, sealable, marked I/O, insulation group II.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What are the tripping mechanisms used in the S200M miniature circuit breakers?
The S200M circuit breakers utilise a delayed thermal tripping mechanism for overload protection and an electromechanic tripping mechanism for short circuit protection.
What is the maximum breaking capacity of the S200M circuit breakers?
The S200M circuit breakers have a rated ultimate short-circuit breaking capacity of up to 25 kA at 230 V AC and 15 kA at 400/440 V AC.
What current ratings are available for the S200M circuit breakers?
The S200M circuit breakers are available with a rated current of up to 63 A.
What types of terminal connections do the S200M circuit breakers support?
The S200M circuit breakers feature screw terminals that accept busbar 10/10 mm², flexible cables from 0.75–25 mm², and rigid cables from 0.75–35 mm².
Can auxiliary contacts be mounted on the S200M circuit breakers?
Yes, a bottom-fitting auxiliary contact can be mounted on the S200M to save 50% space.
What is the mechanical and electrical endurance of the S200M circuit breakers?
The S200M circuit breakers have a mechanical and electrical endurance of 20,000 AC cycles.
Are the S200M circuit breakers compliant with any standards?
Yes, all MCBs in the S200M range comply with IEC/EN 60898-1 and IEC/EN 60947-2. See the manufacturer's data sheet for standards and approvals.