Do you need some help?

Call us now on: 01706 242050

ABB XT4L 160 4 pole Low MCCB Adjustable Thermal-Magnetic Release In=160A Ii=1600A

MPN: 1SDA068394R1

Alt. SKU: XT4L 160 TMA 160-1600 4p F F InN=100%

Special Price £1,021.04 £850.87 Regular Price £1,570.84

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA068394R1]

The TMAX XT4L 160 fixed four-pole circuit breaker features front terminals and a thermomagnetic release (TMA R 160) with adjustable trip settings ranging from 800 to 1600 A. It includes a fully rated neutral pole, ensuring reliable protection and compatibility in three-phase electrical installations requiring precise overload and short-circuit protection.

Technical Specification

  • Function: Four-pole moulded case circuit breaker with thermomagnetic release (TMA R 160).
  • Rated Current: 160 A.
  • Rated Operational Voltage: 690 V AC, 750 V DC.
  • Contact Configuration: Fixed four-pole with front bolt terminals.
  • Connecting Capacity: Busbar 85–200 mm².
  • Impulse Withstand Voltage: 8 kV.
  • Short-Circuit Breaking Capacity (Ics/Icu): Up to 150 kA at 220–240 V AC, decreasing to 20 kA at 690 V AC.
  • Mechanical Durability: 25,000 cycles.
  • Electrical Durability: 8,000 cycles at 120 cycles per hour.
  • Tightening Torque: 8 N·m for terminals.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4L?
The rated current is 160 A.
What is the maximum operational voltage for this circuit breaker?
The maximum operational voltage is 690 V AC and 750 V DC.
What is the connecting capacity for busbars?
The connecting capacity for busbars is 85–200 mm².
What is the short-circuit breaking capacity?
The short-circuit breaking capacity is up to 150 kA at 220–240 V AC, decreasing to 20 kA at 690 V AC.
How many mechanical and electrical cycles can this breaker endure?
The mechanical durability is 25,000 cycles, and the electrical durability is 8,000 cycles at 120 cycles per hour.
What is the tightening torque for the terminals?
The tightening torque for the terminals is 8 N·m.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068394R1
Barcode 8015644023003
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 160A
Alternative Product SKU XT4L 160 TMA 160-1600 4p F F InN=100%
Write Your Own Review
You're reviewing:ABB XT4L 160 4 pole Low MCCB Adjustable Thermal-Magnetic Release In=160A Ii=1600A