Why Choose the Moulded Case Circuit Breaker [1SDA061688R1]

The TMAX T6N 800A fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. It incorporates a solid-state release mechanism, ensuring precise and reliable protection in AC applications. Certified to UL and CSA standards, the PR221DS-LS/I R 800 model delivers robust performance and compatibility with a range of industrial electrical systems.

Technical Specification

  • Type: Moulded Case Circuit Breaker, Fixed Four-Pole with Front Terminals.
  • Rated Current (Iₙ): 800 A.
  • Rated Operational Voltage: 600 V AC.
  • Rated Insulation Voltage (Uᵢ): 1000 V.
  • Impulse Withstand Voltage (Uᵢₘₚ): 8 kV.
  • Interrupting Rating acc. to UL489: 65 kA at 240 V AC, 35 kA at 480 V AC, 20 kA at 600 V AC.
  • Mechanical Durability: 20,000 cycles at 120 cycles per hour.
  • Release Type: Solid-state EL release, PR221DS-LS/I.
  • Power Loss per Pole: 32 W at rated operating conditions.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T6N 800?
The rated current is 800 A.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 600 V AC.
What type of release does the TMAX T6N 800 use?
It uses a solid-state EL release, model PR221DS-LS/I.
What is the interrupting rating for this circuit breaker?
The interrupting rating is 65 kA at 240 V AC, 35 kA at 480 V AC, and 20 kA at 600 V AC.
How many mechanical cycles can this breaker endure?
It has a mechanical durability of 20,000 cycles at 120 cycles per hour.
What is the power loss per pole at rated operating conditions?
The power loss per pole is 32 W.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA061688R1
Barcode 8015644642273
Manufacturer ABB
Number of Poles 4 Pole
Amperage 800A
Alternative Product SKU T6N 800 UL/CSA PR221DS-LS/I 800 4p F F
Product Lead Time Please contact us for a delivery time