Why Choose the Moulded Case Circuit Breaker [1SDA061680R1]

The TMAX T6H 800A fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. Equipped with a solid-state release, it offers precise and reliable protection in AC applications. Certified to UL and CSA standards, this model PR222DS/P-LSIG R 600 ensures compatibility and safety in demanding electrical systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker with solid-state release.
  • Number of Poles: 4 Pole (4P) fixed.
  • Rated Current: 600 A.
  • Rated Operational Voltage: 600 V AC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Interrupting Capacity (UL489): 200 kA at 240 V AC, 65 kA at 480 V AC, 35 kA at 600 V AC.
  • Terminal Type: Front fixed terminals.
  • Mechanical Durability: 20,000 operating cycles at 120 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX T6H?
The rated current is 600 A.
How many poles does the C.BREAKER TMAX T6H have?
It has 4 poles (4P).
What is the interrupting capacity of this circuit breaker?
The interrupting capacity is 200 kA at 240 V AC, 65 kA at 480 V AC, and 35 kA at 600 V AC.
What type of terminals does the C.BREAKER TMAX T6H use?
It features front fixed terminals.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 600 V AC.
What is the mechanical durability of the C.BREAKER TMAX T6H?
It has a mechanical durability of 20,000 operating cycles at 120 cycles/hour.
What standards and approvals does the C.BREAKER TMAX T6H conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA061680R1
Barcode 8015644642198
Manufacturer ABB
Number of Poles 3 Pole
Amperage 600A
Alternative Product SKU T6H 800 UL/CSA PR222DS/P-LSIG 600 4p F F
Product Lead Time Please contact us for a delivery time