We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
P1RC2P63AC300 - RES.CURRENT DEV.2P 63A IDN 300MA TYPE AC
MPN: P1RC2P63AC300
Why Choose the P1RC2P63AC300?
The Lovato P1RC2P63AC300 residual current operated circuit breaker (RCCB) delivers dependable AC leakage protection in a compact, 2‑module footprint. This 2P, type AC device is rated at 63 A with a 300 mA residual current, and conforms to IEC/EN/BS 61008‑1. With 400 V rated insulation and 4 kV impulse withstand, it suits a wide range of compliant distribution and control applications.
Engineered for real‑world conditions, it operates from −35 to +70 °C and up to 2000 m altitude, with IP20 frontal protection and pollution degree 2. Low power dissipation of 3.78 W per pole aids thermal management. Terminal screws tighten to 1.8–2 Nm, and the 185 g unit carries a Sustainability certification for conscientious specification.
Key Benefits
- Compact 2-module design optimises DIN rail space in panels.
- Two-pole configuration for use on two conductors.
- Type AC residual characteristic for standard alternating current leakage faults.
- 63 A rated current supports higher load circuits confidently.
- 300 mA sensitivity provides dependable residual current protection.
- IEC/EN/BS 61008-1 conformity ensures recognised safety performance.
- Wide −35 to +70 °C operating range for challenging environments.
- 4 kV impulse withstand and 400 V insulation for robustness.
Technical Specification
- Rated insulation voltage Ui (IEC/EN): 400 V
- Rated impulse withstand voltage Uimp: 4 kV
- Power dissipation per pole (max): 3.78 W
- Operating temperature: -35 to +70 °C
- Storage temperature: -40 to 80 °C
- Max altitude: 2000 m
- Terminal tightening torque: 1.8 to 2 Nm
- Weight: 185 g
- IP degree (frontal): IP20
- Pollution degree: 2
What’s Included
- Residual current operated circuit breaker (RCCB) unit
- Installation and safety information
- Product datasheet (PDF, via manufacturer link)
- Original packaging
Applications
- Residual current protection for AC circuits compliant with IEC/EN/BS 61008-1
- Distribution boards and control panels with 2-module DIN allocation
- Two-wire circuits requiring a 2P, type AC RCCB
- Switchgear and panel assemblies operating within −35 to +70 °C
Frequently Asked Questions
What type of residual current characteristic does this RCCB have?
What are the rated current and residual sensitivity?
Which standards does it meet?
What environmental conditions can it operate in?
What is the frontal IP rating and terminal torque?
Safety note: Installation must be performed by a qualified electrician with power isolated. Follow IEC/EN/BS 61008-1 and the manufacturer’s instructions; tighten terminals to 1.8–2 Nm.
| Manufacturer Part Number | P1RC2P63AC300 |
|---|---|
| Manufacturer | Lovato |
| Barcode | 8013975204719 |