Standard delivery
£8 ex VAT · free over £200UK parcel delivery is £8 ex VAT, or free on orders over £200 ex VAT.
Heavier items may be charged at a weight-based or pallet rate, shown at checkout.
Danfoss 131B6929 VLT HVAC Drive FC-102, a 110 kW / 150 HP three phase 380-480 V AC variable frequency drive with IP21 / Type 1 enclosure, integrated RFI filter and graphical local control panel for HVAC fan, pump and building services motor control applications.
The Danfoss 131B6929 is a 110 kW / 150 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D1, IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.
This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 110 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 110 kW | |
|---|---|---|
| Phase | Three Phase | |
| IP Rating | IP21 | |
| Series | VLT HVAC Drive FC-102 | |
| Part number | 131B6929 | |
| Model code | FC-102P110T4E21H2XGXXXXSXXXXAXBXCXXXXDX | |
| Rated output power | 110 kW / 150 HP | |
| Output current | 212 A | |
| Input voltage | 380–480 V AC | |
| Input phases | 3-phase | |
| Output phases | 3-phase | |
| Supply frequency | 50 / 60 Hz | |
| Protection rating | IP21 / Type 1 | |
| Frame size | D1 | |
| RFI filter | Integrated RFI filter (H2) | |
| Brake chopper | Not included | |
| PCB coating | Not coated | |
| Mains option | No mains option | |
| Local control panel | Graphical local control panel included | |
| Net weight | Approx. 101 kg | |
| Gross weight | Approx. 116 kg | |
| EAN | 5702427349964 |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.
FC-102P110T4E21H2XGXXXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 110 kW / 150 HP | P110 |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP21 / UL Type 1 | E21 |
| RFI filter Position 16–17 | RFI class A2 (C3) | H2 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |
We use cookies
We use essential cookies to run this site, your basket and checkout. With your permission we'd also like to use analytics and advertising cookies to understand how the site is used and to measure our adverts.