Danfoss 131B8593 VLT HVAC Drive FC-102 frequency converter, a 75 kW / 100 HP three phase variable speed drive for HVAC motor control applications with IP21 / Type 1 protection.
£4,351.05
The Danfoss 131B8593 is a 75 kW / 100 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame C2, IP21 / UL Type 1 unit, suitable for mounting in clean, dry indoor plant rooms.
This configuration has RFI class A2 (C3), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.
Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.
Same configuration, different power
Same 75 kW rating, other enclosures
Tick the specs you need, then view products that match.
| Power | 75 kW | |
|---|---|---|
| Voltage | 480 V | |
| Phase | Three Phase | |
| IP Rating | IP21 | |
| EMC Filter | Industrial | |
| Series | VLT® HVAC Drive FC-102 | |
| SKU | 131B8593 | |
| Product type | Variable speed drive / frequency converter | |
| Rated output power | 75 kW / 100 HP | |
| Input voltage | 380–480 V AC | |
| Input phases | 3-phase | |
| kVA rating | 102 kVA | |
| Continuous output current | 147 A / 130 A | |
| Intermittent output current | 162 A / 143 A | |
| Power loss | 1384 W | |
| Protection rating | IP21 / Type 1 | |
| RFI filter | H2, RFI Class A2 (C3) | |
| Brake chopper | No brake chopper | |
| Control panel | Graphical local control panel | |
| PCB coating | Not coated PCB | |
| Mains option | No mains option | |
| Software | Latest release standard software | |
| Frame size | C2 | |
| Dimensions (H × W × D) | approx. 780 × 370 × 332 mm | |
| Net weight | approx. 52.69 kg | |
| Gross weight | approx. 56.03 kg |
Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.
Yes. The IP21 / UL Type 1 enclosure is designed for direct mounting.
FC-102P75KT4E21H2XGXXXXSXXXXAXBXCXXXXDX
G fitted / defines this unit X not fitted / standard
| Product series Position 1–6 | VLT HVAC Drive FC 102 | FC-102 |
|---|---|---|
| Power size Position 7–10 | 75 kW / 100 HP | P75K |
| Mains voltage Position 11–12 | 3 × 380–480 V AC | T4 |
| Enclosure Position 13–15 | IP21 / UL Type 1 | E21 |
| RFI filter Position 16–17 | RFI class A2 (C3) | H2 |
| Brake / Safe Stop Position 18 | No brake chopper | X |
| Local control panel Position 19 | Graphical LCP 102 | G |
| PCB coating Position 20 | Standard (uncoated) PCBs | X |
| Mains option Position 21 | No mains option | X |
| Adaptation A Position 22 | Standard cable entries | X |
| Adaptation B Position 23 | Standard | X |
| Software release Position 24–27 | Latest standard release | SXXX |
| Software language Position 28 | Standard language package | X |
| A option (fieldbus) Position 29–30 | No fieldbus option | AX |
| B option (I/O) Position 31–32 | No B option | BX |
| C0 option Position 33–34 | No C0 option | CX |
| C1 option Position 35 | No C1 option | X |
| C option software Position 36–37 | None | XX |
| D option Position 38–39 | No D option | DX |