131B6549 Danfoss VLT FC-102 HVAC Drive 110 kW / 150 HP, 380 - 480 VAC, IP00

131B6549 Danfoss VLT FC-102 HVAC Drive 110 kW / 150 HP, 380 – 480 VAC, IP00

Danfoss 131B6549 VLT HVAC Drive FC 102, rated at 110 kW / 150 HP for 380-480 V AC three-phase HVAC motor control applications, supplied as an IP00 chassis drive with RFI Class A1/C2 filter, graphical local control panel, no brake chopper and no mains option.

SKU: 131B6549Alt SKU: FC-102P110T4E00H4XGXXXXSXXXXAXBXCXXXXDXMPN: 131B6549
This product has been discontinued A direct replacement is available below.
134F0376 Danfoss VLT HVAC Drive 110 kW/150HP 380-480VAC IP20 Replacement product Danfoss VLT HVAC Drive 110KW/150HP 380-480VAC IP20 SKU: 134F0376 £5,766.20 ex VAT View

Manufacturer Lead Time

£6,274.40

Danfoss 131B6549 at a glance

The Danfoss 131B6549 is a 110 kW / 150 HP VLT HVAC Drive FC 102 for 3 × 380–480 V AC supplies, made for the fans, pumps and compressors in building services. It is a frame D3, IP00 / chassis unit, built for mounting inside a control panel or enclosure.

This configuration has RFI class A1 (C2), no brake chopper, and a graphical LCP 102 control panel. The full type code is decoded alongside the FAQs.

Sizing and installation

  • Enclosure: IP00 / chassis — built for mounting inside a control panel or enclosure.
  • EMC: RFI class A1 (C2). Check the permitted screened motor cable length in the Danfoss FC 102 Design Guide.

FC 102 features for HVAC

  • Built-in RS-485 protocols: Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee — connects to most building management systems without an option card.
  • Fire Mode keeps the drive running during an emergency, for example to keep smoke-extract fans turning.
  • Automatic Energy Optimisation (AEO) cuts motor losses at part load — Danfoss quotes a further 5–15% saving.
  • Pump and fan functions: sleep mode, dry-pump, end-of-curve and broken-belt detection, plus a built-in cascade controller for pump sets.
  • Built-in DC coils limit mains harmonics (EN 61000-3-12).
  • Smart Logic Controller for simple sequencing without a PLC.

Where the energy saving comes from

Centrifugal fans and pumps follow the affinity laws: absorbed power falls with the cube of speed. Running at 80% speed needs roughly half the power of full speed (0.8³ ≈ 0.51, before motor and drive losses) — which is why speed control pays back faster on fans and pumps than almost any other load.

Other sizes and enclosures

Same configuration, different power

This drive110 kWDanfoss 131B6549IP00 / chassis · frame D3
Larger160 kWDanfoss 131B6938IP00 / chassis · frame D4View drive →

Same 110 kW rating, other enclosures

Typical applications

✓  Supply and extract fans in air-handling units ✓  Chilled- and hot-water circulation pumps ✓  Cooling towers and condenser fans ✓  Booster sets and multi-pump stations ✓  Ventilation and smoke-extract systems

Technical Specifications

Tick the specs you need, then view products that match.

Power 110 kW
Voltage 480 V
Phase Three Phase
IP Rating IP00
EMC Filter Commercial
Model code FC-102P110T4E00H4XGXXXXSXXXXAXBXCXXXXDX
Drive series VLT HVAC Drive FC 102
Product type Variable frequency drive / HVAC inverter drive
Power rating 110 kW / 150 HP
Supply voltage 380–480 V AC
Input phase Three-phase
Enclosure rating IP00 / chassis
Frame size D3
Control panel Graphical Local Control Panel
RFI filter Class A1 / C2
Brake chopper No brake chopper
Mains option No mains option
A option No A option
B option No B option
C1 option No C1 option
D option No D option
PCB coating Not coated PCB

Frequently asked questions

Which communication protocols are built in?

Danfoss FC, Modbus RTU, BACnet MS/TP, Metasys N2 and FLN Apogee over the built-in RS-485 port. This unit has no fieldbus option card fitted, so PROFIBUS, PROFINET, EtherNet/IP or BACnet/IP would need an MCA option card.

Does this drive need to go in an enclosure?

Yes. IP00 / chassis drives are designed to be mounted inside a control panel or enclosure. For wall mounting without a panel, choose an IP55 or IP66 version.

Type code decoded

FC-102P110T4E00H4XGXXXXSXXXXAXBXCXXXXDX

G fitted / defines this unit   X not fitted / standard

Product series
Position 1–6
VLT HVAC Drive FC 102FC-102
Power size
Position 7–10
110 kW / 150 HPP110
Mains voltage
Position 11–12
3 × 380–480 V ACT4
Enclosure
Position 13–15
IP00 / chassisE00
RFI filter
Position 16–17
RFI class A1 (C2)H4
Brake / Safe Stop
Position 18
No brake chopperX
Local control panel
Position 19
Graphical LCP 102G
PCB coating
Position 20
Standard (uncoated) PCBsX
Mains option
Position 21
No mains optionX
Adaptation A
Position 22
Standard cable entriesX
Adaptation B
Position 23
StandardX
Software release
Position 24–27
Latest standard releaseSXXX
Software language
Position 28
Standard language packageX
A option (fieldbus)
Position 29–30
No fieldbus optionAX
B option (I/O)
Position 31–32
No B optionBX
C0 option
Position 33–34
No C0 optionCX
C1 option
Position 35
No C1 optionX
C option software
Position 36–37
NoneXX
D option
Position 38–39
No D optionDX