We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Mersen Surge Protector Type 2 SPD 2 Pole 120 Volt 20KA TNS
MPN: 83020120
Alt. SKU: STPT2-40K150V-2P
Why Choose the STPT2-40K150V-2P Surge Protection Device?
Engineered for reliable protection of single-phase TN-S electrical installations, the STPT2-40K150V-2P Type 2 SPD offers robust surge suppression with a maximum discharge current of 40kA (8/20), ensuring continuity and equipment safety against transient overvoltages.
This compact, pluggable 2-pole device fits seamlessly into 2 modules, supports 120V nominal voltage, and allows quick replacement and easy maintenance, making it ideal for precision-driven commercial or industrial applications demanding consistent surge protection.
Technical Specifications
- Item number: 83020120
- Catalogue No: STPT2-40K150V-2P
- Description: Surge Protection Device Type 2, 40kA Imax (8/20), 1Ph+N, 120/-V, 2+0 TNS, 2 Poles, Pluggable, 2 Modules
- EAN/UPC Code: 8435297851035
- RoHS Compliant: Yes
- IEC SPD Type: Class II
- UL SPD Type: Type 2 Component Assembly
- Format: Pluggable
- Nominal Operating Volt Rating (Un): 120
- AC or DC: AC
- Nominal Discharge Current (In) (8/20): 20 kA
- Max Discharge Current : Imax (8/20): 40 kA
- Protection Modes: L-PE / N-PE
- System Configuration: TNS
- Short Circuit Withstand (ISCCR): 25 kA
- Indication System: Yes
- Indication System Type: Green (OK) / Not green (replace)
- Number of Poles: 2-Pole
- Torque Rating: 3 Nm
- Max. Back-Up Fuse: 125 A [gG]
- Housing Material: PA66 CT1
- MOV Response Time: ≤25
- Installation Mounting: DIN rail
- VPR L-G: 700 V
- VPR N-G: 700 V
- VPR L-N: 1200 V
- Replacement Plug L1: 83020001
- Product Width: 36 mm
- Product Length: 70 mm
- Product Height: 90 mm
- Sell Pack Quantity: 1 EA
- Sell Pack Weight: 0.226 kg
- Sell Pack Width: 42 mm
- Sell Pack Length: 117 mm
- Sell Pack Height: 90 mm
- Product group: Power Line SPDs
- Product Weight: 0.195 kg
Product Code: 83020120
Key Benefits
- High surge current capacity with 40kA maximum discharge current for superior protection.
- Compact and pluggable design allows easy installation and quick replacement.
- Clear visual indication system for status monitoring (Green = OK, Not green = replace).
- Compatible with single-phase TN-S systems ensuring broad application suitability.
- Durable housing material (PA66 CT1) for long-lasting performance.
- DIN rail mounting simplifies integration into existing electrical panels.
Compatibility
The STPT2-40K150V-2P is designed for use in single-phase TN-S electrical systems with a nominal operating voltage of 120V AC. It fits standard DIN rail mounting and is compatible with backup fuses up to 125 A [gG]. Its pluggable format ensures compatibility with existing 2-module spaces in commercial and industrial distribution boards.
Applications
- Commercial electrical distribution boards requiring surge protection.
- Industrial single-phase TN-S installations.
- Protection of sensitive electronic equipment from transient overvoltages.
- Replacement and maintenance of existing Type 2 surge protection devices.
- Use in environments with frequent transient surges or lightning activity.
Frequently Asked Questions
What is the maximum surge current this device can handle?
The STPT2-40K150V-2P can handle a maximum discharge current (Imax) of 40kA (8/20 μs waveform).
Can this device be used in three-phase systems?
No, this device is specifically designed for single-phase TN-S systems.
How does the indication system work?
The device features a green indicator showing operational status; if the indicator is not green, the device should be replaced.
Is the device RoHS compliant?
Yes, the STPT2-40K150V-2P is RoHS compliant.
What is the mounting method for this SPD?
It is designed for DIN rail mounting, allowing easy installation in standard electrical enclosures.
Common Search Terms
surge protection device, SPD, Type 2 SPD, 40kA surge protector, single-phase surge protector, TN-S system SPD, pluggable surge protector, DIN rail SPD, 120V surge protection, industrial surge protector
| Manufacturer Part Number | 83020120 |
|---|---|
| Packed Quantity | 1 |
| Barcode | 8435297851035 |
| Height | 70mm |
| Width | 36mm |
| Depth | 90mm |
| HS Code | 85363090 |
| Country of Manufacture | Spain |
| Manufacturer | Mersen |
| Number of Poles | 2 Pole |
| Voltage | 120V |
| Maximum Continuous Voltage | 150V |
| Nominal Discharge Current | 20Ka |
| System Type | TNS |
| Alternative Product SKU | STPT2-40K150V-2P |

Protection system of coordinated stages: Type 1, 2 and 3 SPDs
The SPDs of a surge protection system must be able to withstand the discharged current and provide a Ures level (residua l voltage) lower than the Ue peak voltage that the equipment can withstand. Most of the times it is not possible to achieve this with just one SPD, especially because the intensity of the surge is not known, and because of the induction of overvoltages when conductors exceed 10m.
The optimal system of protection is the 3-STEP approach, in which successive stages are combined in the performance of high discharge capacity devices and devices with an optimal voltage protection level (low). This is addressed by the definition of "Types" or "Classes" of SPDs according to the type of transient pulses to which each protected zone in the installation is subject to.