The softstarter PSTX210-600-70 has a rated maximum operational current of 210 A with an operating voltage span from 208...600 V AC. The rated control voltage is between 100...250 V AC at 50/60 Hz. PSTX features a three-phase control soft start and stop through a voltage or a torque ramp. It has built-in bypass for easy installation and energy saving. A RUN, TOR and Event signal is available from relay outputs in NO (normally open state). The PSTX has functions such as current limit, kickstart, analog output, EOL, motor heating and pump cleaning. PSTX also features features jog, braking, stand-still brake, diagnostics, sequence start and emergency/fire pump mode as standard.To interact with PSTX, it has a detachable full graphic display with IP66 and 4x outdoor rating. There are four ways to communicate with PSTX. It can be done by hardwire inputs Start/Stop/Reset of fault, and by three programmable digital inputs. Another popular option is the built-in Fieldbus communication Modbus RTU and incl optional ANYBUS modules with every major protocol such as for example Profinet, Profibus, Modbus TCP, Ethernet IP and others. Another way to communicate with PSTX is to use an external adaptor and a Fieldbus plug. PSTX is the complete alternative for any motor starting application. It’s suitable for medium to large-sized three-phase motors with nominal currents from 30...1250 A inline connection or 52...2160 A inside delta connection. Typical applications are, for example, pumps, fans, compressors, and conveyors.
Technical Specification
- Function: Soft start and stop with voltage or torque ramp; built-in bypass; multiple protection and diagnostic functions including electronic overload and current limit.
- Rated Voltage: 208–600 V AC operational voltage.
- Rated Current: 210 A in-line connection; 360 A inside delta connection.
- Control Voltage: 100–250 V AC at 50/60 Hz, control circuit 24 V DC.
- Contact Configuration: Relay outputs available for RUN, BYPASS, FAULT, and OVERLOAD signals (NO).
- Degree of Protection: Main terminals IP00; detachable full graphic display rated IP66, 4x outdoor protection.
- Terminal Type and Size: Main circuit connection via bars with 10.2 mm hole; control circuit terminals accept rigid cables up to 2.5 mm²; tightening torque 25 N·m.
- Communication: Supports Modbus RTU, Modbus TCP, Ethernet IP, EtherCAT, DeviceNet, CANopen, Profibus, Profinet, BACnet-IP/MSTP.
- Mechanical Data: Weight 13.3 kg; built for medium to large three-phase motors (30–1250 A inline, 52–2160 A delta).
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the maximum operational current for the PSTX210-600-70?
What is the operating voltage range for this softstarter?
What types of motors is the PSTX suitable for?
What communication protocols does the PSTX support?
What is the degree of protection for the detachable display?
What are the control voltage specifications for the PSTX?
What type of signals can be obtained from the relay outputs?
| Manufacturer Part Number | 1SFA898112R7000 |
|---|---|
| Barcode | 7320500501504 |
| Max Rated Current | 210 Amps |
| Motor Power (kW) at 400V | 110Kw |
| Motor Power (kW) at 500V | 132Kw |
| Product Image | For Illustration Purposes Only |
| KW Rating | 110kW |
| Manufacturer | ABB |
| Alternative Product SKU | PSTX210-600-70 |
| Product Lead Time | Delivery 7-10 Days |