We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
ABB t16-0.41 thermal overload relay 0.31a - 0.41a
MPN: 1SAZ711201R1014
Alt. SKU: T16-0.41
Why Choose the T16-0.41 [1SAZ711201R1014]
The T16-0.41 thermal overload relay provides cost-effective electromechanical protection for motor main circuits. It delivers dependable, rapid response to overload conditions and phase failure, with a trip class 10 rating. Key features include temperature compensation, a normally closed trip contact, a normally open signal contact, selectable automatic or manual reset, a trip-free mechanism, integrated STOP function, and clear trip indication. Designed for direct mounting on mini or block contactors, the relay ensures seamless integration, with single mounting kits available as accessories.
Technical Specification
- Function: Thermal overload relay for motor protection with trip class 10, phase failure detection, and selectable automatic/manual reset.
- Rated Operational Voltage: Main circuit 690 V AC, auxiliary circuit 600 V AC/DC.
- Current Setting Range: 0.31 to 0.41 A.
- Contact Configuration: 3 poles protected, 1 normally closed (NC) trip contact, 1 normally open (NO) signal contact.
- Insulation & Impulse Voltage Ratings: Rated insulation voltage 690 V, impulse withstand voltage 6 kV for both main and auxiliary circuits.
- Degree of Protection: IP20.
- Terminal Type and Cable Size: Supports flexible and solid cables from 0.75 mm² up to 4 mm² with ferrules.
- Tightening Torque: 1 to 1.2 N·m for auxiliary circuit, 1.1 to 1.5 N·m for main circuit terminals.
- Mounting Compatibility: Suitable for direct mounting on mini and block contactors (B6, BC6, B7, BC7, VB6, VBC6, VB7, VBC7, MC1, MC2, AS09, AS12, AS16).
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the function of the T16-0.41 thermal overload relay?
What is the rated operational voltage for this relay?
What is the current setting range for the T16-0.41?
What type of cables can be used with this relay?
How is the T16-0.41 mounted?
What is the degree of protection for this relay?
What should I refer to for standards and approvals?
| Manufacturer Part Number | 1SAZ711201R1014 |
|---|---|
| Amp Range | 0.31A - 0.41A |
| Manufacturer | ABB |
| Alternative Product SKU | T16-0.41 |
| Barcode | 4013614404672 |
| Product Lead Time | Delivery 2/3 days |