Why Choose the SM1P1400?

Engineered for dependable motor circuit protection, the Lovato SM1P1400 motor protection circuit breaker combines thermal and magnetic trip functions in a compact, 3‑pole design. With SKU SM1P1400, it delivers an IEC short‑circuit breaking capacity Icu of 25 kA at 400 V and an adjustable thermal range of 9...14 A, helping you set precise protection aligned to motor full‑load current and installation fault levels.

Conforming to IEC/EN 60947-1, 60947-2 and 60947-4-1, plus UL508 and CSA C22.2 n° 14, this SM1P device offers Ui 690 V and Uimp 6 kV insulation performance. Push‑button control simplifies setup and testing, while durable mechanics provide 100000 cycles. Rated for -20 to +60 °C operation, up to 3000 m altitude, and 2.5–3 Nm terminal torque, it integrates reliably into industrial control panels.

Key Benefits

  • High 25 kA Icu at 400 V for robust short‑circuit protection.
  • Adjustable 9...14 A thermal trip to match motor full‑load current.
  • Combined magnetic and thermal protection for comprehensive motor safety.
  • Three‑pole design suitable for standard three‑phase motor circuits.
  • Wide operating range -20 to +60 °C for challenging environments.
  • Rated Ui 690 V and Uimp 6 kV for strong insulation performance.
  • Push‑button control simplifies testing and manual operation.

Technical Specification

  • Product type designation: SM1P
  • Number of poles: 3
  • Rated insulation voltage Ui (IEC/EN): 690 V
  • Rated impulse withstand voltage Uimp: 6 kV
  • Mechanical life: 100000 cycles
  • Terminal tightening torque: 2.5 to 3 Nm
  • Operating temperature: -20 to +60 °C
  • Storage temperature: -50 to +80 °C
  • Max altitude: 3000 m
  • Weight: 350 g

What’s Included

  • Lovato SM1P motor protection circuit breaker, SKU SM1P1400
  • Installation and safety information sheet
  • Manufacturer datasheet (PDF)

Applications

  • Protection of three‑phase motors requiring 9...14 A adjustable thermal trip settings
  • Motor circuits on 400 V AC systems with up to 25 kA prospective fault levels
  • IEC/EN 60947 compliant industrial control panels and distribution assemblies
  • Installations operating from -20 to +60 °C, up to 3000 m altitude

Frequently Asked Questions

What current range can the SM1P1400 be set to?
The thermal trip adjustment range is 9...14 A, with a rated current In of 14 A.
What is the short-circuit breaking capacity at 400 V AC?
It has an IEC Icu of 25 kA at 400 V AC.
Does this breaker provide both thermal and magnetic protection?
Yes, it offers magnetic and thermal protection for comprehensive motor safeguarding.
Is the SM1P1400 UL Type E certified?
No, it is not certified as UL Type E.
What are the environmental limits for operation?
Operating temperature is -20 to +60 °C, with a maximum altitude of 3000 m.

Safety note: Install and commission only by qualified personnel. Isolate the supply before work, set the thermal dial to the motor full‑load current (9...14 A range), and tighten terminals to 2.5–3 Nm in accordance with the stated standards.