Why Choose the SM1P0650?
Lovato’s SM1P0650 motor protection circuit breaker safeguards three‑phase motor circuits. It offers IEC breaking capacity Icu of 100 kA at 400 V, a thermal trip adjustment range of 4…6.5 A and a rated current of 6.5 A. Combining magnetic and thermal protection with push‑button control, this 3‑pole SM1P series device is specified to protect against overloads and short circuits in industrial installations.
Rated insulation voltage Ui is 690 V with impulse withstand Uimp of 6 kV, and mechanical life is 100000 cycles. Operating limits span −20 to +60 °C, with storage from −50 to +80 °C and installation up to 3000 m altitude. Terminal tightening torque is 2.5 to 3 Nm. Conforms to IEC/EN 60947‑1/‑2/‑4‑1, UL508 and CSA C22.2 n° 14, and carries a Sustainability certification.
Key Benefits
- High Icu 100 kA at 400 V for strong short‑circuit performance
- Adjustable thermal trip range 4…6.5 A for precise motor protection
- 3‑pole configuration suitable for typical three‑phase motor circuits
- Combined magnetic and thermal protection in a single device
- Push‑button control for straightforward testing and operation
- Rated insulation Ui 690 V and Uimp 6 kV for dielectric strength
- Wide operating range −20 to +60 °C; altitude up to 3000 m
- Long mechanical life rated at 100000 operating cycles
Technical Specification
- Product type designation: SM1P
- Number of poles: 3
- Rated insulation voltage Ui (IEC/EN): 690 V
- Rated impulse withstand voltage Uimp: 6 kV
- Mechanical life: 100000 cycles
- Terminal tightening torque: 2.5 to 3 Nm
- Operating temperature: -20 to +60 °C
- Storage temperature: -50 to +80 °C
- Max altitude: 3000 m
- Weight: 350 g
What’s Included
- Lovato SM1P0650 motor protection circuit breaker
- User and safety instructions
Applications
- Three‑phase motor circuits requiring adjustable 4…6.5 A protection
- Motor feeders in industrial control panels and switchboards
- Systems specifying Icu 100 kA at 400 V short‑circuit performance
- Installations conforming to IEC/EN 60947‑1/‑2/‑4‑1 standards
Frequently Asked Questions
What current range can the SM1P0650 be adjusted to?
What is the short‑circuit breaking capacity at 400 V?
What protection functions and control type does it use?
What are the environmental and mechanical limits?
Which standards does it conform to, and is it UL Type E?
Safety note: Install and commission only by qualified personnel. Isolate the supply before work, tighten terminals to 2.5–3 Nm, and observe the stated temperature and altitude limits and relevant standards.
| Manufacturer Part Number | SM1P0650 |
|---|---|
| Barcode | 8013975216187 |
| HS Code | 85362010 |
| Manufacturer | Lovato |