The Lovato GL0250C1 is a three-pole switch disconnector engineered for safe AC isolation and load switching. Rated Ith 250 A with Ui 1000 V and Uimp 12 kV, it delivers robust performance across demanding installations. Designed for flexibility, this GL series device mounts via screw on plate or standard 35 mm DIN rail and conforms to IEC/EN 60947-3 and 60947-1.
High utilitarian ratings support heavy duty switching: AC23A currents of 250 A at 400–690 V and 135 A at 1000 V, with 2500 A making and 2000 A breaking at 400 V. The device achieves a conditional short-circuit current of 100 kA with gG/250 fuses, offers 20,000 mechanical cycles, and operates from -25 to +55 °C up to 3000 m altitude.
Key Benefits
- Three-pole AC isolation compliant with IEC/EN 60947-3.
- 250 A Ith rating for robust thermal performance.
- AC23A currents up to 250 A at 400–690 V.
- 1000 V Ui and 12 kV impulse withstand for high insulation.
- 100 kA conditional short-circuit rating with gG/250 fuse.
- 2500 A making and 2000 A breaking at 400 V.
- Flexible plate or 35 mm DIN rail mounting.
- Long mechanical life: 20,000 operating cycles.
Technical Specification
- Product type designation: GL
- Number of poles: 3
- Operating voltage type: AC
- Ith (IEC): 250 A
- Rated insulation voltage Ui (IEC/EN): 1000 V
- Rated impulse withstand voltage Uimp: 12 kV
- Operating current Ie AC21A 400 V: 250 A
- Operating current Ie AC21A 500 V: 250 A
- Operating current Ie AC21A 690 V: 250 A
- Operating current Ie AC21A 1000 V: 250 A
- Operating current Ie AC22A 400 V: 250 A
- Operating current Ie AC22A 500 V: 250 A
- Operating current Ie AC22A 690 V: 250 A
- Operating current Ie AC23A 400 V: 250 A
- Operating current Ie AC23A 500 V: 250 A
- Operating current Ie AC23A 690 V: 250 A
- Operating current Ie AC23A 1000 V: 135 A
- Power dissipation per pole (max): 6.5 W
- Rated operational power AC23A 400 V: 140 kW
- Rated operational power AC23A 690 V: 250 kW
- Conditional short-circuit current (rms): 100 kA
- Short-circuit protection fuse: gG/250
- Making capacity AC23A 400 V: 2500 A
- Breaking capacity AC23A 400 V: 2000 A
- Mechanical life: 20000 cycles
- Terminal tightening torque: 15 to 22 Nm
- Conductor section (IEC): 70 to 185 mm²
- Operating temperature: -25 to +55 °C
- Storage temperature: -40 to +70 °C
- Max altitude: 3000 m
- Pollution degree: 3
What’s Included
- Lovato GL0250C1 three-pole switch disconnector
- Installation and safety instructions
Applications
- Isolation and load switching in AC circuits
- AC23A duty applications at 400–690 V
- Industrial control panels and power distribution boards
- Maintenance isolation for machinery and plant
- Installations up to 3000 m altitude within -25 to +55 °C
Frequently Asked Questions
What are the AC switching category ratings?
How do I mount the GL0250C1?
What short-circuit protection is required?
What conductor sizes and torque are specified?
What environmental and altitude ratings apply?
Safety note: Install and service only by qualified personnel. De-energise circuits before work, use the specified gG/250 fuse, apply 15–22 Nm terminal torque with 70–185 mm² conductors, and observe IEC/EN limits and temperatures.
| Manufacturer Part Number | GL0250C1 |
|---|---|
| Barcode | 8013975228623 |
| HS Code | 85365080 |
| Manufacturer | Lovato |
| Number of Poles | 3 Pole |
| Amperage | 250A |
| Alternative Product SKU | GL0250 C1 |