GE0160 - 3P SWITCH DISCONNECTOR
MPN: GE0160
Why Choose the GE0160?
The Lovato GE0160 three‑pole switch disconnector delivers dependable isolation for AC circuits up to 160 A. Designed for screw-on plate installation, this GE-series device meets IEC/EN 60947-1 and 60947-3, featuring Ui 1000 V and Uimp 8 kV. With an IP20 frontal degree and robust mechanical life of 30,000 cycles, SKU GE0160 provides reliable on-load disconnection in demanding industrial panels and machinery.
High utilisation categories are supported: AC21A/AC22A/AC23A ratings up to 160 A at 400 V, with AC23A 500 V 125 A and 690 V 80 A. It offers 90 kW at 400 V and 75 kW at 690 V (AC23A), 1600 A making and 1280 A breaking at 400 V, and a 100 kA conditional short-circuit current with gG160 fuse. Operates −25…55 °C, up to 3000 m altitude; terminal torque 13 Nm.
Key Benefits
- Three-pole isolation for AC circuits up to 160 A.
- Complies with IEC/EN 60947-1 and 60947-3 standards.
- High AC23A performance: 90 kW at 400 V, 75 kW at 690 V.
- Robust making 1600 A and breaking 1280 A at 400 V.
- Conditional short-circuit withstand up to 100 kA with gG160 fuse.
- IP20 frontal protection and pollution degree 3 suitability.
- Long mechanical life: 30,000 operating cycles.
Technical Specification
- Product type designation: GE
- Number of poles: 3
- Operating voltage type: AC
- Ith (IEC): 160 A
- Rated insulation voltage Ui (IEC/EN): 1000 V
- Rated impulse withstand voltage Uimp: 8 kV
- Operating current Ie AC21A 400 V: 160 A
- Operating current Ie AC21A 500 V: 160 A
- Operating current Ie AC21A 690 V: 160 A
- Operating current Ie AC22A 400 V: 160 A
- Operating current Ie AC22A 500 V: 160 A
- Operating current Ie AC22A 690 V: 125 A
- Operating current Ie AC23A 400 V: 160 A
- Operating current Ie AC23A 500 V: 125 A
- Operating current Ie AC23A 690 V: 80 A
- Power dissipation per pole (max): 4 W
- Rated operational power AC23A 400 V: 90 kW
- Rated operational power AC23A 690 V: 75 kW
- Conditional short-circuit current (rms): 100 kA
- Short-circuit protection fuse: gG160
- Making capacity AC23A 400 V: 1600 A
- Breaking capacity AC23A 400 V: 1280 A
- Mechanical life: 30000 cycles
- Terminal tightening torque (max): 13 Nm
- Operating temperature: -25 to 55 °C
- Storage temperature: -40 to 70 °C
- Max altitude: 3000 m
- IP degree (frontal): IP20
- Pollution degree: 3
What’s Included
- GE0160 three-pole switch disconnector
- Manufacturer data sheet (download)
- Basic installation guidance
Applications
- Incoming isolator in industrial distribution and control panels
- Motor and machinery isolation for maintenance operations
- On-load disconnection of mixed resistive and inductive loads
- Feeder isolation in process, HVAC, and plant equipment
Frequently Asked Questions
Which standards does the GE0160 comply with?
How is the GE0160 mounted?
What is the frontal IP rating?
What operating temperature range is supported?
What short-circuit protection is recommended?
Safety note: Always isolate power before installation or maintenance, observe the stated ratings and standards, use appropriate short-circuit protection, and tighten terminals to the specified torque.
| Manufacturer Part Number | GE0160 |
|---|---|
| Manufacturer | Lovato |
| HS Code | 85365080 |
| Barcode | 8013975175651 |