We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
GAZM160ET6 - 3P 160A CHANGEOVER METAL ENCLOSED SWITCH
MPN: GAZM160ET6
Why Choose the GAZM160ET6?
Engineered for reliable source transfer, the Lovato GAZM160ET6 three-pole line changeover switch delivers secure I-0-II selection in a robust IP65 metal enclosure. Rated Ith 160 A with AC operation, it offers 1000 V Ui and 8 kV Uimp resilience. Compact at 200x300x120mm, it suits demanding environments and control panels, supporting dependable mains/backup switching and distribution duties.
Performance spans duty categories: AC21A to 160 A up to 690 V, AC22A to 160 A at 400 V, and AC23A to 125 A at 400 V with 55 kW power. With 50 kA conditional short-circuit using gG160 fusing and IP65 frontal sealing, it meets IEC/EN 60947-3/-1. Terminals take 4–70 mm² at 5–6 Nm; operation −25 to +55 °C, to 3000 m.
Key Benefits
- IP65 metal enclosure protects against dust and water ingress.
- 160 A Ith and Ui 1000 V for demanding AC installations.
- Robust AC23A performance: 55 kW at 400 V, 45 kW at 690 V.
- High withstand: 8 kV impulse and 50 kA conditional short-circuit.
- Long service life: 30,000 mechanical cycles, 1,500 electrical (AC21A).
- Wide wiring range 4–70 mm² with 5–6 Nm tightening torque.
- Operates −25 to +55 °C, up to 3000 m altitude.
- I-0-II selector provides clear, safe source changeover indication.
Technical Specification
- Product type designation: GAZM
- Number of poles: 3
- Operating voltage type: AC
- Ith (IEC): 160 A
- Rated insulation voltage Ui (IEC/EN): 1000 V
- Rated impulse withstand voltage Uimp: 8 kV
- Operating current Ie AC21A 400 V: 160 A
- Operating current Ie AC21A 500 V: 160 A
- Operating current Ie AC21A 690 V: 160 A
- Operating current Ie AC22A 400 V: 160 A
- Operating current Ie AC22A 500 V: 125 A
- Operating current Ie AC22A 690 V: 125 A
- Operating current Ie AC23A 400 V: 125 A
- Operating current Ie AC23A 500 V: 100 A
- Operating current Ie AC23A 690 V: 47 A
- Power dissipation per pole (max): 12 W
- Rated operational power AC23A 400 V: 55 kW
- Rated operational power AC23A 690 V: 45 kW
- Conditional short-circuit current (rms): 50 kA
- Short-circuit protection fuse: gG160
- Making capacity AC23A 400 V: 1250 A
- Breaking capacity AC23A 400 V: 1000 A
- Mechanical life: 30000 cycles
- Electrical life AC21A: 1500 cycles
- Terminal tightening torque: 5 to 6 Nm
- Conductor section (IEC): 4 to 70 mm²
- Operating temperature: -25 to +55 °C
- Storage temperature: -40 to +70 °C
- Max altitude: 3000 m
- IP degree (frontal): IP65
- Pollution degree: 3
What’s Included
- Three-pole line changeover switch in IP65 metal enclosure (GAZM160ET6)
- Installation and safety information
- Manufacturer product datasheet
Applications
- Mains to generator changeover and backup power selection
- Industrial distribution boards and switchgear panels
- Motor and load switching within AC23A ratings
- HVAC, pumps and plant equipment source transfer
Frequently Asked Questions
What is the current rating of the GAZM160ET6?
What are the enclosure dimensions and protection level?
Which standards does this changeover switch conform to?
What short-circuit protection should be used?
What conductor sizes and terminal torque are supported?
Safety note: Installation must be carried out by qualified personnel. Isolate all power, use the specified gG160 fusing, and operate only within the stated electrical, environmental and altitude limits.
| Manufacturer Part Number | GAZM160ET6 |
|---|---|
| Manufacturer | Lovato |
| Packed Quantity | 1 |
| HS Code | 85365080 |
| Barcode | 8013975235461 |
| Amperage | 160A |
| Number of Poles | 3 Pole |