Why Choose the GAZM025?
Lovato’s GAZM025 switch disconnector delivers reliable on-load isolation in a robust IP65 metal enclosure. This three-pole, 25 A unit features a high-visibility red/yellow rotary handle and compact 150x200x120 mm footprint, ideal for machinery and panel installations. Rated for AC operation with Ui 1000 V and Uimp 8 kV, it provides dependable performance in demanding industrial environments.
With AC21A, AC22A and AC23A utilisation categories up to 690 V at 25 A, the GAZM025 supports switching of resistive and inductive loads. It offers 100,000 mechanical and electrical life cycles, 10 kA conditional short-circuit current with gG25 fuse, and IP65 protection. Terminals accept 0.75–16 mm² conductors with 1.8–2 Nm torque; operating temperature −25 to +55 °C.
Key Benefits
- IP65 metal enclosure safeguards against dust and water jets.
- Three-pole, 25 A AC isolator for dependable on-load disconnection.
- High-visibility red/yellow rotary handle for clear operator control.
- Rated Ui 1000 V and Uimp 8 kV for robust insulation.
- AC21A/AC22A/AC23A performance up to 690 V at 25 A.
- 100,000 mechanical and electrical life cycles reduce maintenance.
- Accepts 0.75–16 mm² conductors; 1.8–2 Nm terminal torque.
Technical Specification
- Product type designation: GAZM
- Number of poles: 3
- Operating voltage type: AC
- Ith (IEC): 25 A
- Rated insulation voltage Ui (IEC/EN): 1000 V
- Rated impulse withstand voltage Uimp: 8 kV
- Operating current Ie AC21A 400 V: 25 A
- Operating current Ie AC21A 500 V: 25 A
- Operating current Ie AC21A 690 V: 25 A
- Operating current Ie AC22A 400 V: 25 A
- Operating current Ie AC22A 500 V: 25 A
- Operating current Ie AC22A 690 V: 25 A
- Operating current Ie AC23A 400 V: 25 A
- Operating current Ie AC23A 500 V: 25 A
- Operating current Ie AC23A 690 V: 25 A
- Power dissipation per pole (max): 0.4 W
- Rated operational power AC23A 400 V: 11 kW
- Rated operational power AC23A 690 V: 22 kW
- Conditional short-circuit current (rms): 10 kA
- Short-circuit protection fuse: gG25
- Making capacity AC23A 400 V: 400 A
- Breaking capacity AC23A 400 V: 320 A
- Mechanical life: 100000 cycles
- Electrical life AC21A: 100000 cycles
- Terminal tightening torque: 1.8 to 2 Nm
- Conductor section (IEC): 0.75 to 16 mm²
- Operating temperature: -25 to +55 °C
- Storage temperature: -40 to +70 °C
- Max altitude: 3000 m
- IP degree (frontal): IP65
- IP degree of protection: IP65
- Pollution degree: 3
What’s Included
- Lovato GAZM025 enclosed switch disconnector (IP65 metal enclosure)
- Rotating red/yellow handle pre-fitted to enclosure
- Downloadable product datasheet and documentation
Applications
- On-load isolation of AC circuits in industrial panels
- Machine and equipment main or local isolator duties
- Switching of resistive and inductive loads per AC21A–AC23A ratings
- Environments requiring IP65 protection against dust and water jets
- Motor load isolation up to 22 kW at 690 V AC23A
Frequently Asked Questions
What is the rating of the Lovato GAZM025 switch disconnector?
What IP protection does this enclosed switch provide?
Which standards does the GAZM025 conform to?
What are the utilisation category ratings?
Which fuse is recommended for short-circuit protection?
Safety note: Install and commission only by qualified personnel. Isolate the supply before work, follow IEC/EN standards and local regulations, and use the recommended gG25 fuse for short-circuit protection.
| Manufacturer Part Number | GAZM025 |
|---|---|
| Manufacturer | Lovato |
| HS Code | 85365080 |
| Barcode | 8013975235065 |