Danfoss 131N0224 VLT HVAC Drive FC-101 90kW Three Phase 380 - 480 VAC IP54
MPN: 131N0224
Alt. SKU: FC-101P90KT4P5AH3XAXXXXSXXXXAXBXCXXXXDX
Why Choose the Danfoss FC‑101 HVAC Basic Drive (Part 131N0224)?
The Danfoss FC‑101 (P90K), part number 131N0224, provides rugged 90 kW (125 HP) three-phase motor control for HVAC, compressor, and pump applications. It supplies 380–480 VAC and is built into an IP54 chassis-mounted enclosure (Frame I8; not Type 12). This variant includes a built-in Class A1/B (IEC C1) RFI filter, alpha‑numeric Local Control Panel (LCP), and features a non‑coated PCB. It ships without brake chopper or mains option—ideal for integrated panel installations with onboard UI and EMC compliance.
Technical Specifications
| Part Number | 131N0224 |
|---|---|
| Model Code | FC‑101P90KT4P5AH3XAXXXXSXXXXAXBXCXXXXAXBXCXXXXDX |
| Power Rating | 90 kW / 125 HP |
| Voltage | 380–480 VAC, three‑phase |
| Enclosure | IP54 chassis (Frame I8; not Type 12) |
| RFI Filter | Class A1/B (IEC C1) |
| Brake Chopper | Not included |
| Local Control Panel (LCP) | Included — alpha‑numeric |
| PCB Coating | Not coated |
| Net Weight | ≈ 62.2 kg |
| Gross Weight | ≈ 65.9 kg |
| Frame Size | I8 |
| Certifications | CE, UL/cUL, RoHS; supports UL LZGH2 (A2L refrigerants) |
Frequently Asked Questions
- Which EMC/RFI compliance does it meet?
- Is a Local Control Panel included?
- Is the PCB coated?
- What are typical applications?
Typical Applications
- OEM HVAC panels for high‑power fans, pumps, and compressors
- Panel installations needing built-in EMC filtering and onboard display
- Indoor use in dusty or humid settings thanks to IP54 enclosure
Key Features
- 90 kW / 125 HP performance at 380–480 VAC
- IP54-rated chassis enclosure (Frame I8) suitable for harsh indoor environments
- Built-in Class A1/B RFI filter with DC choke—no external filter needed for motor cables ≤ 20 m
- Alpha‑numeric LCP included for setup, diagnostics, and control
- Compatible with both induction and permanent‑magnet motors via EC+ optimized V/f and sensorless vector control
- Fire Mode (Safe Torque Off), Flying Start, and auto‑restart capabilities
- Automatic Energy Optimizer saving ~3–5 % runtime energy
- Communication protocols supported: BACnet MS/TP, Modbus RTU, N2, LonWorks via RS‑485
| Manufacturer Part Number | 131N0224 |
|---|---|
| Barcode | 5710107089864 |
| Height | 770mm |
| Width | 370mm |
| Depth | 335mm |
| Brake - Safe-Stop | No brake chopper |
| Coating PCB | Not coated PCB |
| Control Panel | Alpha Numeric LCP |
| Filter | (H3) RFI Class A1/B (C1) |
| Input Phases | Three Phase |
| Degree of protection (IP) | IP54 |
| KW Rating | 90kW |
| Output Phases | Three phase |
| VSD Range | Danfoss VLT HVAC Drive FC-101 |
| Manufacturer | Danfoss |
| Alternative Product SKU | FC-101P90KT4P5AH3XAXXXXSXXXXAXBXCXXXXDX |