We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Danfoss 131N0197 VLT HVAC Drive FC-101 22kW Three Phase 380 - 480 VAC IP54
MPN: 131N0197
Alt. SKU: FC-101P22KT4E5AH2XAXXXXSXXXXAXBXCXXXXDX
Why Choose the Danfoss FC‑101 HVAC Basic Drive (Part 131N0197)?
The Danfoss FC‑101 (P22K), part number 131N0197, provides 22 kW (30 HP) three‑phase motor control specifically for HVAC, pump, and compressor systems. It operates on 380–480 VAC and features an IP54 enclosure (Frame I6). This variant includes a **built‑in RFI filter (Class A2 / IEC C3)**, an **alpha‑numeric LCP**, but ships with an **uncoated PCB**, and has no brake chopper or mains option.
Technical Specifications
| Part Number | 131N0197 |
|---|---|
| Model Code | FC‑101P22KT4E5AH2XAXXXXSXXXXAXBXCXXXXDX |
| Power Rating | 22 kW / 30 HP |
| Input Voltage | 380–480 VAC, three‑phase |
| Enclosure | IP54 chassis (Frame I6) |
| RFI Filter | Class A2 / IEC C3 |
| Brake Chopper | Not included |
| Local Control Panel (LCP) | Included — alpha‑numeric interface |
| PCB Coating | Not coated |
| Net Weight | ≈ 27 kg |
| Gross Weight | ≈ 27.3 kg |
| Certifications | CE, UL/cUL, RoHS; UL 60335‑2‑40 LZGH2 (A2L refrigerants) |
Frequently Asked Questions
- How much energy can this drive save?
- What EMC/RFI compliance level does it offer?
- Which motor types are supported?
- Can it integrate with BMS systems?
Typical Applications
- OEM HVAC panel builds and retrofits
- Commercial fan, pump, and compressor control
- Ventilation, refrigeration, and booster systems requiring IP54 protection
Key Features
- 22 kW / 30 HP output at 380–480 VAC
- IP54 enclosure (Frame I6) for protection in dusty or damp environments
- Built-in Class A2 (IEC C3) RFI filter—no external filter needed
- Alpha‑numeric LCP included for easy parameter setup
- Supports BACnet MS/TP, Modbus RTU, N2, and LonWorks via RS‑485
- Automatic Energy Optimizer yields ~3–5 % energy savings
- Compatible with both induction and permanent‑magnet motors (V/f & sensorless vector control)
- Fire Mode, Safe Torque Off, and Flying Start functionality included
| Manufacturer Part Number | 131N0197 |
|---|---|
| Barcode | 5702427810686 |
| Height | 650mm |
| Width | 242mm |
| Depth | 260mm |
| Brake - Safe-Stop | No brake chopper |
| Coating PCB | Not coated PCB |
| Control Panel | Alpha Numeric LCP |
| Filter | RFI Filter |
| Input Phases | Three Phase |
| Degree of protection (IP) | IP54 |
| KW Rating | 22kW |
| Output Phases | Three phase |
| VSD Range | Danfoss VLT HVAC Drive FC-101 |
| Manufacturer | Danfoss |
| Alternative Product SKU | FC-101P22KT4E5AH2XAXXXXSXXXXAXBXCXXXXDX |