We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
Danfoss 131N0195 VLT HVAC Drive FC-101 18.5kW Three Phase 380 - 480 VAC IP54
MPN: 131N0195
Alt. SKU: FC-101P18KT4E5AH2XAXXXXSXXXXAXBXCXXXXDX
Why Choose the Danfoss FCâ101 HVAC Basic Drive (Partâ¯131N0195)?
The Danfoss FCâ101 (P18K), part number 131N0195, delivers 18.5â¯kW (25â¯HP) threeâphase motor control tailored for HVAC, pump, and compressor systems. It supports 380â480â¯VAC input and is installed in an IP54 enclosure (Frame I4, not Typeâ¯12). This variant includes an alphaânumeric Local Control Panel (LCP), has no brake chopper, no mains option, features an uncoated PCB, and does not include optional software or hardware enhancements. Builtâin RFI filtering is enabled (Class A2 / IECâ¯C3).
Technical Specifications
| Part Number | 131N0195 |
|---|---|
| Model Code | FCâ101P18KT4E5AH2XAXXXXSXXXXAXBXCXXXXDX |
| Power Rating | 18.5â¯kW / 25â¯HP |
| Voltage | 380â480â¯VAC, threeâphase |
| Enclosure | IP54 chassis (Frameâ¯I4) |
| RFI Filter | Classâ¯A2 (IECâ¯C3) |
| Brake Chopper | Not included |
| Local Control Panel (LCP) | Included â alphaânumeric |
| PCB Coating | Not coated |
| Net Weight | ââ¯13.8â¯kg |
| Gross Weight | ââ¯15.6â¯kg |
| Frame Size | I4 |
| Certifications | CE, UL/cUL, RoHS; UL LZGH2 certification for A2L refrigerants compliant (ULâ¯60335â2â40/â89) |
Frequently Asked Questions
- How much energy can this drive save?
- What EMC/RFI compliance level does it provide?
- Which motor types does it support?
- Can it integrate with building management systems?
Typical Applications
- OEM and retrofit HVAC panel installations involving fan, pump, or compressor control
- Commercial ventilation, chilled water, and refrigeration systems with integrated EMC and user interface
- Use in dust or moisture-prone environments, leveraging IP54 protection
Key Features
- 18.5â¯kW / 25â¯HP output at 380â480â¯VAC
- IP54 chassis (Frame I4) designed for harsh environments
- Built-in Classâ¯A2 (IECâ¯C3) RFI filterâeliminates need for external filtering for â¤â¯20â¯m cable
- Alphaânumeric Local Control Panel included, enhancing setup and diagnostics
- Supports BACnet MS/TP, Modbus RTU, N2, and LonWorks protocols via RSâ485
- Automatic Energy Optimizer saves ~3â5â¯% energy from start-up
- Compatible with both induction and permanent-magnet motors through EC+ optimized V/f and sensorless vector control
- Fire Mode (Safe Torque Off), Flying Start, and auto-restart functionality included
| Manufacturer Part Number | 131N0195 |
|---|---|
| Barcode | 5710107088591 |
| Height | 476mm |
| Width | 180mm |
| Depth | 290mm |
| Brake - Safe-Stop | No brake chopper |
| Coating PCB | Not coated PCB |
| Control Panel | Alpha Numeric LCP |
| Filter | RFI Filter |
| Input Phases | Three Phase |
| Degree of protection (IP) | IP54 |
| KW Rating | 18.5kW |
| Output Phases | Three phase |
| VSD Range | Danfoss VLT HVAC Drive FC-101 |
| Manufacturer | Danfoss |