Why Choose the S203MT-K1.6UC [2CDS273065R0257]

S203MT-K1,6UC MCB K-Char., 10kA, 1,6A, 3P

Technical Specification

  • Function: 3-pole miniature circuit breaker (MCB), K-characteristic.
  • Current Rating: 1.6 A.
  • Rated Short-Circuit Breaking Capacity: 10 kA at 230 V AC, 400 V AC, 440 V AC, and 440 V DC.
  • Voltage Rating: Maximum operating voltage 500 V DC / 480Y/277 V AC (UL/CSA).
  • Contact Configuration: 3 poles (3P) with red ON / green OFF indication.
  • Insulation & Dielectric Strength: Dielectric test voltage 2 kV (50/60 Hz, 1 min).
  • Mechanical Endurance: 20,000 operating cycles.
  • Electrical Endurance: 20,000 AC cycles, 1,500 DC cycles.
  • Terminal Type and Size Range: Screw terminals; busbar 10/10 mm², flexible 0.75–25 mm², rigid 0.75–35 mm².
  • Tightening Torque: 2.8 N·m (main circuit 18 in·lb UL/CSA).

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the function of the S203MT-K1,6UC MCB?
The S203MT-K1,6UC is a 3-pole miniature circuit breaker (MCB) with a K-characteristic.
What is the current rating of this MCB?
The current rating is 1.6 A.
What is the rated short-circuit breaking capacity?
The rated short-circuit breaking capacity is 10 kA at 230 V AC, 400 V AC, 440 V AC, and 440 V DC.
What are the terminal types and size ranges for this MCB?
It features screw terminals with a busbar size of 10/10 mm², flexible cables from 0.75–25 mm², and rigid cables from 0.75–35 mm².
What is the maximum operating voltage for this MCB?
The maximum operating voltage is 500 V DC / 480Y/277 V AC (UL/CSA).
What is the tightening torque for the terminals?
The tightening torque is 2.8 N·m (18 in·lb UL/CSA).
What is the mechanical and electrical endurance of this MCB?
The mechanical endurance is 20,000 operating cycles, and the electrical endurance is 20,000 AC cycles and 1,500 DC cycles.
More Information
Manufacturer Part Number 2CDS273065R0257
Amperage 1.6A
Number of Poles 3 Pole
HS Code 85362010
Country of Manufacture Germany
Manufacturer ABB
Alternative Product SKU S203MT-K1.6UC
Barcode 4013614447785