ABB s203m-k40 mcb s200p 3p k type 40a
MPN: 2CDS273001R0557
Alt. SKU: S203M-K40
Why Choose the S203M-K40 [2CDS273001R0557]
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Technical Specification
- Function: Current limiting miniature circuit breaker with thermal and electromechanical tripping mechanisms for overload and short circuit protection.
- Rated Current: Up to 63 A.
- Voltage Ratings: 230/400 V AC; Maximum operating voltage UL/CSA 125 V DC, 480Y/277 V AC.
- Contact Configuration: 3 poles (3P) with red ON/green OFF indication.
- Breaking Capacity: 25 kA at 230 V AC, 15 kA at 400 and 440 V AC.
- Terminal Type and Capacity: Screw terminals; suitable for flexible and rigid conductors 0.75 to 35 mm², busbar 10/10 mm².
- Mechanical Endurance: 20,000 cycles.
- Actuator: Toggle type, black insulated, sealable with I/O marking.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the maximum rated current for the S200M miniature circuit breakers?
What are the available breaking capacities for the S200M?
Can the S200M be used in residential applications?
What type of conductors can be used with the S200M terminals?
What tripping mechanisms are used in the S200M circuit breakers?
Is it possible to mount auxiliary contacts on the S200M?
What is the mechanical endurance of the S200M circuit breakers?
| Manufacturer Part Number | 2CDS273001R0557 |
|---|---|
| Amperage | 40A |
| Number of Poles | 3 Pole |
| HS Code | 85362010 |
| Country of Manufacture | Germany |
| Manufacturer | ABB |
| Alternative Product SKU | S203M-K40 |
| Barcode | 4016779601337 |