System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Technical Specification
- Function: Miniature circuit breaker with thermal and electromechanic tripping for overload and short circuit protection.
- Voltage Ratings: Rated for up to 440 V AC, with ultimate short-circuit breaking capacity up to 25 kA at 230 V AC.
- Current Rating: Rated current up to 63 A; specific model S203M-K10 rated for 10 A.
- Contact Configuration: 3 poles (3P) with contact position indication (Red ON / Green OFF).
- Terminal Type and Size Range: Screw terminals supporting flexible cables 0.75–25 mm², rigid cables 0.75–35 mm², busbar up to 10/10 mm².
- Insulation & Dielectric Withstand: Insulation group II; dielectric test voltage 2 kV at 50/60 Hz for 1 minute.
- Mechanical Endurance: Rated for 20,000 operation cycles.
- Tightening Torque: 2.8 N·m for terminals; 18 in·lb for UL/CSA standards.
- Standards Compliance: IEC/EN 60898-1 and IEC/EN 60947-2 certified for residential, commercial and industrial use.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What are the tripping mechanisms used in the S200M miniature circuit breakers?
What is the maximum breaking capacity of the S200M circuit breakers?
What is the rated current capacity of the S200M circuit breakers?
Can auxiliary contacts be mounted on the S200M circuit breakers?
What cable sizes are supported by the S200M circuit breakers?
What standards do the S200M circuit breakers comply with?
| Manufacturer Part Number | 2CDS273001R0427 |
|---|---|
| Amperage | 10A |
| Number of Poles | 3 Pole |
| Manufacturer | ABB |
| Alternative Product SKU | S203M-K10 |
| Barcode | 4016779601221 |
| Product Lead Time | Delivery 7/10 Days |