We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
ABB s203-k10 mcb s200p 3 pole k type 10amp
MPN: 2CDS253001R0427
Alt. SKU: S203-K10
Why Choose the S203-K10 [2CDS253001R0427]
System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Technical Specification
- Function: Miniature circuit breaker with thermal-magnetic trip for overload and short circuit protection.
- Voltage Ratings: Rated operating voltage up to 440 V AC; maximum operating voltage UL/CSA 480Y/277 V AC, 110 V DC.
- Current Rating: 10 A rated current.
- Contact Configuration: 3 poles (3P) with red ON / green OFF indication.
- Breaking Capacity: Ultimate breaking capacity 20 kA at 230 V AC; service breaking capacity 15 kA at 230 V AC.
- Terminal Type and Capacity: Screw terminals, supports flexible and rigid conductors from 0.75 to 35 mm² and busbar 10/10 mm².
- Mechanical and Electrical Endurance: 20,000 cycles each.
- Tightening Torque: 2.8 N·m (18 in·lbf for UL/CSA).
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What are the tripping mechanisms used in the S200 miniature circuit breakers?
What is the maximum breaking capacity of the S200 circuit breakers?
What types of configurations are available for the S200 circuit breakers?
What is the rated current and voltage for the S200 circuit breakers?
What is the cable capacity for the terminals of the S200 circuit breakers?
How many mechanical and electrical cycles can the S200 circuit breakers endure?
Are the S200 circuit breakers compliant with any standards?
| Manufacturer Part Number | 2CDS253001R0427 |
|---|---|
| Amperage | 10A |
| Number of Poles | 3 Pole |
| HS Code | 85362010 |
| Country of Manufacture | Germany |
| Manufacturer | ABB |
| Alternative Product SKU | S203-K10 |
| Barcode | 4016779496148 |