Why Choose the S202M-K63 [2CDS272001R0607]

System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.

Technical Specification

  • Function: Current limiting miniature circuit breaker with thermal and electromechanic tripping for overload and short circuit protection.
  • Voltage Ratings: Up to 440 V AC; 230 V AC breaking capacity 25 kA, 400 V AC breaking capacity 15 kA.
  • Current Rating: Rated current up to 63 A.
  • Contact Configuration: 2 poles (2P) with red ON / green OFF indication.
  • Terminal Type: Failsafe bi-directional cylinder-lift screw terminals.
  • Connecting Capacity: Busbar 10 mm²; flexible cables 0.75–25 mm²; rigid cables 0.75–35 mm².
  • Mechanical Endurance: 20,000 operating cycles.
  • Dielectric Test Voltage: 2 kV at 50/60 Hz for 1 minute.
  • Actuator: Toggle type, black insulated, sealable, marked I/O.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What are the tripping mechanisms used in the S200M miniature circuit breakers?
The S200M circuit breakers utilise a delayed thermal tripping mechanism for overload protection and an electromechanic tripping mechanism for short circuit protection.
What is the maximum breaking capacity of the S200M at 230 V AC?
The maximum breaking capacity of the S200M at 230 V AC is 25 kA.
What is the rated current capacity of the S200M circuit breakers?
The rated current capacity of the S200M circuit breakers is up to 63 A.
What types of cables can be connected to the S200M circuit breakers?
The S200M circuit breakers can connect flexible cables ranging from 0.75 to 25 mm² and rigid cables from 0.75 to 35 mm².
Are the S200M circuit breakers suitable for industrial applications?
Yes, all S200M circuit breakers comply with IEC/EN 60898-1 and IEC/EN 60947-2, making them suitable for residential, commercial, and industrial applications.
What is the mechanical endurance of the S200M circuit breakers?
The mechanical endurance of the S200M circuit breakers is rated at 20,000 operating cycles.
Can auxiliary contacts be mounted on the S200M circuit breakers?
Yes, a bottom-fitting auxiliary contact can be mounted on the S200M to save 50% space.