We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
ABB s202m-k25 mcb s200p 2 pole k type 25amp
MPN: 2CDS272001R0517
Alt. SKU: S202M-K25
Why Choose the S202M-K25 [2CDS272001R0517]
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.
Technical Specification
- Function: Current limiting miniature circuit breaker with thermal and electromechanical trip for overload and short circuit protection.
- Voltage & Current Ratings: Rated ultimate short-circuit breaking capacity 25 kA at 230 V AC, 15 kA at 400/440 V AC; rated current up to 63 A.
- Contact Configuration: 2 poles (2P).
- Terminal Type & Size Range: Screw terminals suitable for busbars 10/10 mm², flexible cables 0.75–25 mm², rigid cables 0.75–35 mm².
- Insulation & Dielectric Strength: Dielectric test voltage 2 kV (50/60 Hz, 1 min); actuator insulation group II.
- Mechanical Endurance: Rated for 20,000 operating cycles.
- Contact Position Indication: Red ON / Green OFF for clear status display.
- Tightening Torque: 2.8 N·m (standard), 18 in·lb (UL/CSA compliant).
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What types of tripping mechanisms do the S200M miniature circuit breakers use?
What are the available configurations for the S200M circuit breakers?
What is the maximum breaking capacity of the S200M circuit breakers?
What is the rated current capacity of the S200M circuit breakers?
What types of cables can be used with the S200M circuit breakers?
How can I mount auxiliary contacts on the S200M circuit breakers?
Do the S200M circuit breakers comply with any standards?
| Manufacturer Part Number | 2CDS272001R0517 |
|---|---|
| Amperage | 25A |
| Number of Poles | 2 Pole |
| HS Code | 85362010 |
| Country of Manufacture | Germany |
| Manufacturer | ABB |
| Alternative Product SKU | S202M-K25 |
| Barcode | 4016779600767 |