ABB s202-k10 mcb s200p 2 pole k type 10a amp
MPN: 2CDS252001R0427
Alt. SKU: S202-K10
Why Choose the S202-K10 [2CDS252001R0427]
System pro M compact S200 miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 6 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200 comply with IEC/EN 60898-1, IEC/EN 60947-2, UL1077 allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200 to save 50% space.
Technical Specification
- Function: Two tripping mechanisms - thermal for overload and electromechanic for short circuit protection.
- Voltage Ratings: Up to 480Y/277 V AC and 110 V DC.
- Current Rating: Rated up to 63 A.
- Contact Configuration: 2 poles (2P).
- Breaking Capacity: Rated ultimate short-circuit breaking capacity up to 20 kA (230 V AC), rated service breaking capacity 15 kA (230 V AC).
- Insulation & Dielectric Test: Dielectric test voltage 2 kV at 50/60 Hz for 1 minute.
- Terminal Type & Size: Failsafe bi-directional cylinder-lift screw terminals, connecting capacity up to 35 mm² rigid and 25 mm² flexible conductors.
- Mechanical & Electrical Endurance: 20,000 mechanical and 20,000 electrical AC cycles.
- Actuator: Toggle type, sealed and marked I/O, red ON / green OFF indication.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What are the tripping mechanisms used in the S200 miniature circuit breakers?
What is the maximum breaking capacity of the S200 circuit breakers?
What are the available current ratings for the S200 series?
Can auxiliary contacts be mounted on the S200 circuit breakers?
What is the terminal size and type for the S200 circuit breakers?
What standards do the S200 circuit breakers comply with?
| Manufacturer Part Number | 2CDS252001R0427 |
|---|---|
| Amperage | 10A |
| Number of Poles | 2 Pole |
| Manufacturer | ABB |
| Alternative Product SKU | S202-K10 |
| Barcode | 4016779507394 |
| Product Lead Time | Delivery 2/3 Days |