Why Choose the S201M-D2NA [2CDS271103R0021]

System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.

Technical Specification

  • Function: Current limiting miniature circuit breaker with thermal and electromechanic tripping for overload and short circuit protection.
  • Voltage Ratings: Up to 400 V AC, maximum operating voltage 480Y/277 V AC, 60 V DC.
  • Current Rating: Rated currents up to 63 A; example SKU is 1P+N, 2 A.
  • Contact Configuration: Pole configurations include 1P, 1P+N, 2P, 3P, 3P+N, and 4P; example model is 1P+N.
  • Breaking Capacity: Rated ultimate breaking capacity up to 25 kA at 133 V AC and 15 kA at 230/400 V AC.
  • Terminal Type and Size: Screw terminals, accommodating busbar 10/10 mm², flexible cables 0.75–25 mm², rigid cables 0.75–35 mm².
  • Mechanical and Electrical Endurance: 20,000 operational cycles each.
  • Actuator: Toggle type with red ON / green OFF indication, black insulation, sealable.
  • Installation Size: Complies with DIN 43880 size 1.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What are the tripping mechanisms used in the S200M miniature circuit breakers?
The S200M circuit breakers utilise a delayed thermal tripping mechanism for overload protection and an electromechanic tripping mechanism for short circuit protection.
What are the available configurations for the S200M circuit breakers?
The S200M circuit breakers are available in configurations of 1P, 1P+N, 2P, 3P, 3P+N, and 4P.
What is the maximum breaking capacity of the S200M circuit breakers?
The rated ultimate breaking capacity is up to 25 kA at 133 V AC and 15 kA at 230/400 V AC.
What is the cable capacity for the S200M circuit breakers?
The S200M circuit breakers can accommodate flexible cables from 0.75 to 25 mm² and rigid cables from 0.75 to 35 mm².
What is the rated current for the S200M circuit breakers?
The S200M circuit breakers have rated currents up to 63 A.
Can auxiliary contacts be mounted on the S200M circuit breakers?
Yes, bottom-fitting auxiliary contacts can be mounted on the S200M to save 50% space.
What standards do the S200M circuit breakers comply with?
All S200M circuit breakers comply with IEC/EN 60898-1 and IEC/EN 60947-2. See the manufacturer's data sheet for standards and approvals.