Why Choose the OT63F4N2 [1SCA105365R1001]

This 4-pole, front-operated switch-disconnector is base mounted and designed for DIN-rail installation. It features protected clamp terminals for secure wiring connections. Please note that the handle and shaft are supplied separately. This non-fusible switch-disconnector is suitable for reliable isolation in a range of electrical applications.

Technical Specification

  • Function: 4-pole front operated base mounted switch-disconnector, non-fusible, with protected clamp terminals. Handle and shaft not included.
  • Rated Operational Current: 63 A (AC-21A/22A) up to 690 V; 45 A (AC-23A) at 500 V; 20 A (AC-23A) at 690 V.
  • Rated Insulation Voltage (Ui): 750 V IEC/EN 60664-1.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Degree of Protection: Front IP20.
  • Terminal Type and Size Range: Screw terminals; conductors Cu 1.5 to 35 mm² (flexible, solid, stranded, with ferrule).
  • Mechanical Durability: 20,000 operating cycles.
  • Cable Cross-Section: 1.5 to 35 mm² copper conductors.
  • Rated Short-Circuit Making Capacity (Icm): 2.1 kA at 690 V.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the function of this switch-disconnector?
This product is a 4-pole, front operated, base mounted switch-disconnector designed for non-fusible applications.
What is the rated operational current for this switch?
The rated operational current is 63 A (AC-21A/22A) up to 690 V, 45 A (AC-23A) at 500 V, and 20 A (AC-23A) at 690 V.
What is the cable capacity for this switch?
The switch accommodates copper conductors with a cross-section of 1.5 to 35 mm², including flexible, solid, and stranded conductors with ferrules.
Is the handle and shaft included with the switch?
No, the handle and shaft are not included with the switch.
What is the degree of protection for this switch?
The degree of protection is IP20 for the front of the switch.
What are the rated insulation and impulse withstand voltages?
The rated insulation voltage (Ui) is 750 V and the rated impulse withstand voltage (Uimp) is 8 kV.
What standards does this switch conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SCA105365R1001
HS Code 85365080
Amperage 63A
Number of Poles 4 Pole
Country of Manufacture Finland
Manufacturer ABB
Mount Type Base mounted
Alternative Product SKU OT63F4N2
Barcode 6417019393094
Write Your Own Review
You're reviewing:ABB ot63f4n2 63 amp load break switch 4 pole