Why Choose the OT40F6 [1SCA104936R1001]

6-pole, front-operated switch-disconnector designed for base mounting and DIN-rail installation. This non-fusible switch features protected clamp terminals for secure wiring connections. Please note that the handle and shaft are supplied separately.

Technical Specification

  • Function: 6-pole, front operated, base mounted switch-disconnector, non-fusible, with protected clamp terminals; handle and shaft not included.
  • Rated Operational Voltage: Up to 750 V (main circuit).
  • Rated Operational Current: 40 A for AC-21A and AC-22A; 23 A (380-500 V) and 12 A (690 V) for AC-23A.
  • Insulation Voltage (Ui): 750 V as per IEC/EN 60664-1.
  • Impulse Withstand Voltage (Uimp): 8 kV.
  • Degree of Protection: Front IP20.
  • Terminal Type and Cable Size: Screw terminals; Cu cable cross-section 0.75 to 10 mm² (flexible, ferruled, solid, stranded).
  • Mechanical Durability: 20,000 operations.
  • Rated Conditional Short-Circuit Current: 50 kA (with appropriate fuses, ≤415 V and 690 V).

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the function of this switch-disconnector?
This is a 6-pole, front operated, base mounted switch-disconnector designed for non-fusible applications.
What is the rated operational voltage and current?
The rated operational voltage is up to 750 V, with a rated operational current of 40 A for AC-21A and AC-22A; 23 A at 380-500 V and 12 A at 690 V for AC-23A.
What type of terminals does this product have?
The switch-disconnector features screw terminals with a cable size capacity of 0.75 to 10 mm² for flexible, ferruled, solid, and stranded copper cables.
What is the degree of protection for this device?
The device has a front degree of protection rated at IP20.
What is the mechanical durability of this switch?
The mechanical durability is rated for 20,000 operations.
What is the rated conditional short-circuit current?
The rated conditional short-circuit current is 50 kA, provided appropriate fuses are used for voltages up to 415 V and 690 V.
Are the handle and shaft included with the switch?
No, the handle and shaft are not included with the switch-disconnector.
More Information
Manufacturer Part Number 1SCA104936R1001
HS Code 85365080
Amperage 40A
Number of Poles 6 Pole
Country of Manufacture Finland
Manufacturer ABB
Mount Type Base mounted
Alternative Product SKU OT40F6
Barcode 6417019390765