We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
ABB f204 a-63/0.03 110v 4p rcd 63a 30ma
MPN: 2CSF204199R1630
Alt. SKU: F204 A-63/0.03 110V
Why Choose the ABB F204 A-63/0.03 110V Residual Current Circuit Breaker?
The ABB F204 A-63/0.03 110V is a high-quality four-pole residual current circuit breaker (RCCB) designed to provide reliable earth fault protection in residential, commercial and industrial electrical installations. As part of the trusted ABB F200 RCCB series, it helps protect people and installations by detecting residual current faults and disconnecting the circuit when leakage current exceeds the rated threshold.
This Type A RCCB detects sinusoidal alternating residual currents and pulsating DC residual currents. Its 63 A rated current and 30 mA residual operating current make it suitable for additional protection against electric shock in modern low voltage electrical systems.
The F204 A-63/0.03 110V is designed with a minimum test button operating voltage of 110 V, making it suitable for installations where 110 V test functionality is required while remaining compatible with standard low voltage applications. Its compact four-pole DIN rail mounting format makes it ideal for professional distribution boards and control panels.
Key Advantages
- Reliable four-pole RCCB for low voltage electrical installations.
- 63 A rated current for residential, commercial and industrial distribution systems.
- 30 mA residual current sensitivity for additional protection against electric shock.
- Type A residual current detection for AC and pulsating DC residual currents.
- 110 V minimum test button operating voltage for specialist installation requirements.
- Compact DIN rail mounting for distribution boards and control panels.
Key Features
- ABB F200 residual current circuit breaker series.
- F204 four-pole RCCB configuration.
- 63 A rated operational current.
- 30 mA rated residual operating current.
- Type A residual current protection.
- 110 V test button operating voltage variant.
- Suitable for 230/400 V AC electrical systems.
- DIN rail mounting with compact modular housing.
Technical Specifications
- Manufacturer: ABB
- Series: F200 RCCB Series
- Model: F204 A-63/0.03 110V
- Manufacturer Part Number: 2CSF204199R1630
- Product type: Residual Current Circuit Breaker (RCCB)
- Residual current type: Type A
- Number of poles: 4P
- Rated current: 63 A
- Rated residual operating current: 30 mA
- Rated operational voltage: 230 / 400 V AC
- Minimum test button operating voltage: 110 V
- Rated insulation voltage: 500 V
- Rated impulse withstand voltage: 4 kV
- Rated conditional short-circuit current: 10 kA
- Protection rating: IP20 terminals / IP40 housing
- Mounting type: DIN rail
- Neutral terminal position: Right
- Electrical endurance: 10,000 operating cycles
- Mechanical endurance: 20,000 operating cycles
- Dimensions (H × W × D): 85 × 70 × 69 mm
- Weight: Approx. 360 g
Reliable Earth Fault Protection for Low Voltage Installations
Residual current circuit breakers continuously monitor the balance between live conductors and neutral. If earth leakage occurs, the RCCB disconnects the circuit quickly to help reduce the risk of electric shock, electrical fire and damage to connected equipment.
The ABB F204 A-63/0.03 110V is designed for installations where dependable Type A residual current protection is required alongside a 110 V minimum test button operating voltage. This makes it a practical choice for professional electrical contractors, panel builders and maintenance engineers working with specialist low voltage distribution systems.
Typical Applications
- Residential electrical distribution boards.
- Commercial power distribution systems.
- Industrial control panels and switchgear assemblies.
- Three-phase low voltage installations.
- Machinery and automation electrical panels.
- Installations requiring 110 V test button operation.
Frequently Asked Questions
What is the ABB F204 A-63/0.03 110V used for?
The ABB F204 A-63/0.03 110V is used to provide residual current protection in low voltage electrical installations, helping disconnect circuits when earth leakage faults are detected.
What does the 30 mA rating mean?
The 30 mA residual operating current means the RCCB is designed to trip when earth leakage reaches this threshold, providing additional protection against electric shock.
What does Type A protection mean?
Type A RCCBs detect sinusoidal alternating residual currents and pulsating DC residual currents, making them suitable for many modern electrical installations.
Why does this RCCB have 110V in the model name?
The 110V designation refers to the minimum operating voltage of the test button, making this variant suitable for installations where 110 V test operation is required.
How is the ABB F204 A-63/0.03 110V installed?
The RCCB mounts directly onto a standard DIN rail within distribution boards, switchboards and electrical control panels.
Trusted by Electrical Professionals Worldwide
ABB F200 residual current circuit breakers are widely trusted by electrical contractors, panel builders and maintenance engineers for dependable earth fault protection across residential, commercial and industrial installations.
| Manufacturer Part Number | 2CSF204199R1630 |
|---|---|
| Amperage | 63A |
| Number of Poles | 4 Pole |
| HS Code | 85363030 |
| Country of Manufacture | Italy |
| Manufacturer | ABB |
| Alternative Product SKU | F204 A-63/0.03 110V |
| Barcode | 8012542342731 |