Why Choose the S303P-B13NA [2CDS383103R0135]

The MCBs S300P series assures protection in industrial installations against overload and short circuits. This product is manufactured according to international IEC and UL standards, for the markets where it is required.

Technical Specification

  • Function: Protection against overload and short circuits in industrial installations.
  • Rated Ultimate Short-Circuit Breaking Capacity: 25 kA at 415 V AC, 15 kA at 440 V AC.
  • Voltage Rating: 480Y/277 V AC maximum operating voltage.
  • Contact Configuration: 3 poles + neutral (3P+N) with right-positioned neutral terminal.
  • Insulation & Dielectric Strength: Dielectric test voltage 2 kV at 50/60 Hz for 1 minute.
  • Terminal Type & Size Range: Screw terminals, busbar 10/10 mm², flexible 0.75–25 mm², rigid 0.75–35 mm².
  • Mechanical and Electrical Endurance: 20,000 cycles each.
  • Actuator: Toggle type with red ON / green OFF indication, insulation group II, sealable.
  • Tightening Torque: 2.8 N·m (standard), 18 in·lb (UL/CSA).

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the primary function of the MCBs S300P series?
The MCBs S300P series provides protection against overload and short circuits in industrial installations.
What is the rated ultimate short-circuit breaking capacity?
The rated ultimate short-circuit breaking capacity is 25 kA at 415 V AC and 15 kA at 440 V AC.
What is the maximum operating voltage for this product?
The maximum operating voltage is 480Y/277 V AC.
What type of terminals does the MCBs S300P series use?
It uses screw terminals with a busbar size of 10/10 mm² and accommodates flexible cables from 0.75–25 mm² and rigid cables from 0.75–35 mm².
How many mechanical and electrical cycles can the MCBs S300P series endure?
The product is rated for 20,000 cycles each for mechanical and electrical endurance.
What type of actuator does the MCBs S300P series feature?
The actuator is a toggle type with red ON and green OFF indication, designed for insulation group II and is sealable.
What is the tightening torque specification for the terminals?
The standard tightening torque is 2.8 N·m (18 in·lb for UL/CSA).
More Information
Manufacturer Part Number 2CDS383103R0135
Packed Quantity 1
Barcode 4016779077293
HS Code 85362010
Country of Manufacture Germany
Manufacturer ABB
Number of Poles 3 Pole + N
Amperage 13A
Alternative Product SKU S303P-B13NA