Why Choose the S302P-K10 [2CDS382001R0427]

The MCBs S300P series assures protection in industrial installations against overload and short circuits. This product is manufactured according to international IEC and UL standards, for the markets where it is required.

Technical Specification

  • Function: Protection against overload and short circuits in industrial installations.
  • Rated Voltage: Up to 480Y/277 V AC and 125 V DC.
  • Breaking Capacity: 25 kA (415 V AC), 15 kA (440 V AC), 25 kA (125 V DC).
  • Poles: 2 poles (2P) with 2 protected poles.
  • Contact Position Indication: Red ON / Green OFF.
  • Terminal Type: Screw terminals with failsafe bi-directional cylinder-lift design.
  • Connecting Capacity: Flexible cables 0.75–25 mm², rigid 0.75–35 mm², busbar 10/10 mm².
  • Electrical Endurance: 20,000 AC cycles.
  • Mechanical Endurance: 20,000 cycles.
  • Tightening Torque: 2.8 N·m (18 in·lb UL/CSA).

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the main function of the MCBs S300P series?
The MCBs S300P series provides protection against overload and short circuits in industrial installations.
What is the rated voltage for the MCBs S300P series?
The rated voltage is up to 480Y/277 V AC and 125 V DC.
What is the breaking capacity of the MCBs S300P series?
The breaking capacity is 25 kA at 415 V AC, 15 kA at 440 V AC, and 25 kA at 125 V DC.
How many poles does the MCBs S300P series have?
The MCBs S300P series features 2 poles (2P) with 2 protected poles.
What is the connecting capacity for cables?
The connecting capacity is flexible cables 0.75–25 mm², rigid cables 0.75–35 mm², and busbar 10/10 mm².
What type of terminals does the MCBs S300P series use?
The MCBs S300P series uses screw terminals with a failsafe bi-directional cylinder-lift design.
What are the electrical and mechanical endurance ratings?
The electrical endurance is 20,000 AC cycles, and the mechanical endurance is also 20,000 cycles.
More Information
Manufacturer Part Number 2CDS382001R0427
Packed Quantity 1
Barcode 4016779078566
HS Code 85362010
Country of Manufacture Germany
Manufacturer ABB
Number of Poles 2 Pole
Amperage 10A
Alternative Product SKU S302P-K10