Do you need some help?

Call us now on: 01706 242050

2CDS382001R0377 ABB S302P-K6 Miniature Circuit Breaker - 2P - K - 6 A

MPN: 2CDS382001R0377

Alt. SKU: S302P-K6

Special Price £69.95 £58.29 Regular Price £127.19

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

This product replaces this item:

Free delivery on orders over £200

Why Choose the S302P-K6 [2CDS382001R0377]

The MCBs S300P series assures protection in industrial installations against overload and short circuits. This product is manufactured according to international IEC and UL standards, for the markets where it is required.

Technical Specification

  • Function: Protection against overload and short circuits in industrial installations.
  • Rated Breaking Capacity: 100 kA for 125 V DC, 400/415/440 V AC; 25 kA for 72 V DC.
  • Number of Poles: 2P (Double Pole).
  • Dielectric Test Voltage: 2 kV at 50/60 Hz for 1 minute.
  • Terminal Type and Capacity: Screw terminals; supports flexible (0.75–25 mm²), rigid (0.75–35 mm²), and busbar 10/10 mm² connections.
  • Contact Position Indication: Red (ON) / Green (OFF).
  • Mechanical and Electrical Endurance: 20,000 cycles each.
  • Actuator Type and Material: Toggle, insulation group II, black, sealable.
  • Tightening Torque: 2.8 N·m (standard), 18 in·lb (UL/CSA).

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the primary function of the MCBs S300P series?
The MCBs S300P series provides protection against overload and short circuits in industrial installations.
What is the rated breaking capacity of this product?
The rated breaking capacity is 100 kA for 125 V DC and 400/415/440 V AC, and 25 kA for 72 V DC.
How many poles does the MCBs S300P series have?
This series features a 2P (Double Pole) configuration.
What is the tightening torque for the terminals?
The standard tightening torque is 2.8 N·m (18 in·lb for UL/CSA).
What types of connections are supported by the terminal?
The terminals support flexible (0.75–25 mm²), rigid (0.75–35 mm²), and busbar 10/10 mm² connections.
What is the dielectric test voltage for this product?
The dielectric test voltage is 2 kV at 50/60 Hz for 1 minute.
What standards does the MCBs S300P series conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 2CDS382001R0377
Packed Quantity 1
Barcode 4016779078634
HS Code 85362010
Country of Manufacture Germany
Manufacturer ABB
Number of Poles 2 Pole
Amperage 6A
Alternative Product SKU S302P-K6