Why Choose the Moulded Case Circuit Breaker [1SDA068567R1]

The TMAX XT4L 160 fixed three-pole circuit breaker features front terminals and an integrated solid-state release, designed for reliable AC protection. Part of the EKIP-LSIG range, this model offers adjustable long-time, short-time, and ground fault protection, rated at 63 A. Its robust construction ensures compatibility with industrial electrical systems, delivering precise and consistent performance in demanding applications.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with solid-state Ekip LSIG release.
  • Rated Operational Voltage: 690 V AC.
  • Rated Current: 63 A.
  • Short-Circuit Breaking Capacity (Icu/Ics): Up to 150 kA at 220-240 V AC, decreasing to 20 kA at 690 V AC.
  • Insulation Voltage (Ui): 1000 V.
  • Impulse Withstand Voltage (Uimp): 8 kV.
  • Contact Configuration: 3 poles (3P).
  • Terminal Type: Front bolt terminals suitable for busbar 85 to 200 mm².
  • Mechanical Durability: 25,000 operating cycles.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4L?
The rated current is 63 A.
What is the short-circuit breaking capacity of this circuit breaker?
The short-circuit breaking capacity is up to 150 kA at 220-240 V AC, decreasing to 20 kA at 690 V AC.
What type of terminals does the C.BREAKER TMAX XT4L have?
It has front bolt terminals suitable for busbar sizes of 85 to 200 mm².
What is the insulation voltage for this circuit breaker?
The insulation voltage is 1000 V.
How many operating cycles can this circuit breaker endure?
The mechanical durability is rated for 25,000 operating cycles.
What is the impulse withstand voltage of the C.BREAKER TMAX XT4L?
The impulse withstand voltage is 8 kV.
Is there any conformity information available for this product?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068567R1
Barcode 8015644024734
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 63A
Alternative Product SKU XT4L 160 Ekip LSIG In=63A 3p F F
Write Your Own Review
You're reviewing:ABB XT4L 160 3 pole Low MCCB Electronic trip unit LSIG Ii=63A