Why Choose the Moulded Case Circuit Breaker [1SDA068537R1]

The TMAX XT4H 160 fixed four-pole circuit breaker features front terminals and an integrated solid-state release, designed for reliable AC protection. Rated at 63 A, this device is compatible with EKIP-I R control units, offering precise tripping characteristics and enhanced operational control. Its robust construction ensures dependable performance in industrial and commercial electrical installations.

Technical Specification

  • Function: Moulded Case Circuit Breaker, four-pole fixed with front terminals.
  • Rated Current: 63 A.
  • Rated Operational Voltage: 690 V AC.
  • Rated Insulation Voltage: 1000 V.
  • Rated Impulse Withstand Voltage: 8 kV.
  • Short-Circuit Breaking Capacity (I cs / I cu): Up to 100 kA at 220-240 V AC, decreasing to 15 kA at 690 V AC.
  • Terminal Connection: Front bolt type, suitable for busbars 85–200 mm², tightening torque 8 N·m.
  • Mechanical Durability: 25,000 cycles.
  • Electrical Durability: 8,000 cycles at 120 cycles per hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4H?
The rated current is 63 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 690 V AC.
What type of terminal connection does this breaker use?
It features front bolt type terminals suitable for busbars of 85–200 mm².
What is the short-circuit breaking capacity of the TMAX XT4H?
It has a short-circuit breaking capacity of up to 100 kA at 220-240 V AC, decreasing to 15 kA at 690 V AC.
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 25,000 cycles.
How many electrical cycles can this breaker handle?
It can handle 8,000 electrical cycles at a rate of 120 cycles per hour.
What standards and approvals does the TMAX XT4H conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068537R1
Barcode 8015644024437
Manufacturer ABB
Number of Poles 4 Pole
Amperage 63A
Alternative Product SKU XT4H 160 Ekip I In=63A 4p F F
Product Lead Time Please contact us for a delivery time