Why Choose the Moulded Case Circuit Breaker [1SDA068502R1]

The TMAX XT4S 160 fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. It is equipped with a solid-state release incorporating EKIP C DIP LSI technology, providing precise protection and enhanced selectivity in AC applications. Rated at 63 A, this breaker ensures reliable performance and compatibility with a wide range of electrical systems.

Technical Specification

  • Function: Moulded Case Circuit Breaker, 4-pole fixed with solid-state release.
  • Rated Current: 63 A.
  • Rated Operational Voltage: 690 V AC.
  • Rated Insulation Voltage (Ui): 1000 V AC.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics): Up to 85 kA at 220-240 V AC; decreasing to 12 kA at 690 V AC.
  • Terminal Type: Front bolt terminals, compatible with busbars 85–200 mm².
  • Mechanical Durability: 25,000 cycles at 240 cycles/hour.
  • Standards Compliance: IEC 60947-2.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4S?
The rated current is 63 A.
What is the maximum operational voltage for this circuit breaker?
The maximum rated operational voltage is 690 V AC.
What type of terminals does the TMAX XT4S feature?
It has front bolt terminals compatible with busbars of 85–200 mm².
What is the short-circuit breaking capacity of this breaker?
It can handle up to 85 kA at 220-240 V AC, decreasing to 12 kA at 690 V AC.
How many mechanical cycles can the TMAX XT4S endure?
The mechanical durability is rated for 25,000 cycles at 240 cycles/hour.
What standards does the C.BREAKER TMAX XT4S comply with?
It complies with IEC 60947-2. See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068502R1