ABB XT4H 250 4 pole High MCCB Adjustable Thermal-Magnetic Release In=250A Ii=2500A

MPN: 1SDA068359R1

Alt. SKU: XT4H 250 TMA 250-2500 4p F F InN=50%

Special Price £1,135.51 £946.26 Regular Price £1,746.95

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA068359R1]

The TMAX XT4H 250 fixed four-pole circuit breaker features front terminals and a thermomagnetic release (TMA R 250) designed for reliable protection. It offers adjustable current settings ranging from 1250 to 2500 A, with the neutral pole rated at 50% of the phase current. This robust device is suitable for demanding industrial and commercial electrical installations requiring precise overload and short-circuit protection.

Technical Specification

  • Function: Fixed four-pole moulded case circuit breaker with thermomagnetic release TMA R 250.
  • Rated Current: 250 A.
  • Rated Operational Voltage: 690 V AC / 750 V DC.
  • Number of Poles: 4 poles with neutral equal to 50% of phase.
  • Rated Insulation Voltage: 1000 V.
  • Rated Impulse Withstand Voltage: 8 kV.
  • Short-Circuit Breaking Capacity: Up to 100 kA at 220-240 V AC, 70 kA at 380-415 V AC, 15 kA at 690 V AC, 70 kA at 250-500 V DC (poles in series).
  • Terminal Type and Size Range: Front terminals with M8 bolts, suitable for busbars 85-200 mm².
  • Mechanical Durability: 25,000 cycles at 240 cycles per hour.
  • Standards: Compliant with IEC 60947-2.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4H?
The rated current is 250 A.
What is the maximum operational voltage for this circuit breaker?
The rated operational voltage is 690 V AC / 750 V DC.
How many poles does the TMAX XT4H have?
The circuit breaker has 4 poles, with the neutral equal to 50% of the phases.
What is the short-circuit breaking capacity of the device?
It has a short-circuit breaking capacity of up to 100 kA at 220-240 V AC, 70 kA at 380-415 V AC, 15 kA at 690 V AC, and 70 kA at 250-500 V DC (poles in series).
What type of terminals does the TMAX XT4H use?
The circuit breaker features front terminals with M8 bolts, suitable for busbars ranging from 85-200 mm².
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 25,000 cycles at 240 cycles per hour.
Is the TMAX XT4H compliant with any standards?
Yes, it is compliant with IEC 60947-2. See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068359R1
Barcode 8015644022655
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 250A
Alternative Product SKU XT4H 250 TMA 250-2500 4p F F InN=50%
Write Your Own Review
You're reviewing:ABB XT4H 250 4 pole High MCCB Adjustable Thermal-Magnetic Release In=250A Ii=2500A