ABB XT4S 250 3 pole Standard MCCB Adjustable Thermal-Magnetic Release In=250A Ii=2500A

MPN: 1SDA068312R1

Alt. SKU: XT4S 250 TMA 250-2500 3p F F

Special Price £750.25 £625.21 Regular Price £1,154.23

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA068312R1]

The TMAX XT4S 250 fixed three-pole circuit breaker features front terminals and a thermomagnetic release (TMA R 250), providing reliable protection for electrical installations. Rated for current settings from 1250 A to 2500 A, it ensures precise overload and short-circuit detection. Designed for compatibility with industrial switchgear, this breaker delivers robust performance and ease of integration in demanding applications.

Technical Specification

  • Function: Thermomagnetic fixed three-pole moulded case circuit breaker with front terminals.
  • Rated Current (In): 250 A.
  • Rated Operational Voltage: 690 V AC / 750 V DC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity: Up to 85 kA AC (220–240 V) and 50 kA DC (250–500 V, poles in series).
  • Terminal Type and Size: Front bolt terminals, suitable for busbars 85–200 mm², tightening torque 8 N·m.
  • Mechanical Durability: 25,000 operating cycles.
  • Standards: Complies with IEC 60947-2.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4S 250?
The rated current (I n) is 250 A.
What is the maximum short-circuit breaking capacity?
Up to 85 kA AC (220–240 V) and 50 kA DC (250–500 V, poles in series).
What type of terminals does this circuit breaker have?
It features front bolt terminals suitable for busbars of 85–200 mm².
What is the tightening torque for the terminals?
The tightening torque is 8 N·m.
What is the mechanical durability of the circuit breaker?
The mechanical durability is rated for 25,000 operating cycles.
What is the rated operational voltage?
The rated operational voltage is 690 V AC / 750 V DC.
Is this product compliant with any standards?
Complies with IEC 60947-2. See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068312R1
Barcode 8015644022181
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 250A
Alternative Product SKU XT4S 250 TMA 250-2500 3p F F