Do you need some help?

Call us now on: 01706 242050

ABB XT4N 160 3 pole Normal MCCB Electronic trip unit I Ii=63A

MPN: 1SDA068128R1

Alt. SKU: XT4N 160 Ekip M Dip I In=63A 3p F F

Special Price £600.30 £500.25 Regular Price £923.53

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA068128R1]

The C.BREAKER TMAX XT4N 160 is a fixed, three-pole circuit breaker featuring front terminals for straightforward installation and maintenance. It incorporates a solid-state release mechanism, providing precise and reliable protection in AC applications. Designed for use with the EKIP M DIP I R system, this breaker is rated at 63 A, ensuring compatibility and robust performance in industrial and commercial electrical installations.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with solid-state release (Ekip M Dip I).
  • Rated Current (In): 63 A.
  • Rated Operational Voltage: 690 V AC.
  • Number of Poles: 3P (three poles).
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics): Up to 65 kA at 220-240 V AC, reducing to 10 kA at 690 V AC.
  • Terminal Type: Front bolt terminals, suitable for busbars 85–200 mm² with M8 screw tightening torque of 8 N·m.
  • Mechanical Durability: 25,000 cycles.
  • Weight: 2.5 kg.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4N?
The rated current is 63 A.
What is the maximum operational voltage for this circuit breaker?
The maximum operational voltage is 690 V AC.
What type of terminals does the TMAX XT4N have?
It has front bolt terminals suitable for busbars 85–200 mm².
What is the short-circuit breaking capacity of this circuit breaker?
It can handle up to 65 kA at 220-240 V AC, reducing to 10 kA at 690 V AC.
How many poles does the TMAX XT4N circuit breaker have?
It is a three-pole (3P) circuit breaker.
What is the mechanical durability of the TMAX XT4N?
The mechanical durability is rated for 25,000 cycles.
What standards and approvals does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068128R1
Barcode 8015644020255
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 63A
Alternative Product SKU XT4N 160 Ekip M Dip I In=63A 3p F F
Write Your Own Review
You're reviewing:ABB XT4N 160 3 pole Normal MCCB Electronic trip unit I Ii=63A