Do you need some help?

Call us now on: 01706 242050

ABB XT4N 160 4 pole Normal MCCB Adjustable Thermal-Magnetic Release In=125A Ii=1250A

MPN: 1SDA068102R1

Alt. SKU: XT4N 160 TMA 125-1250 4p F F InN=50%

Special Price £745.85 £621.54 Regular Price £1,147.46

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA068102R1]

The TMAX XT4N 160 fixed four-pole circuit breaker features front terminals and a thermomagnetic release (TMA R 125) designed for reliable protection. It offers adjustable current ratings from 625 A to 1250 A, with the neutral pole rated at 50% of the phase current. This breaker is engineered for robust performance in three-phase electrical systems, ensuring compatibility and dependable operation in industrial and commercial installations.

Technical Specification

  • Function: Four-pole moulded case circuit breaker with thermomagnetic release TMA R 125.
  • Rated Current (Iₙ): 125 A (setting range 87.5 to 125 A).
  • Rated Voltage (Uᵣ): 690 V AC / 750 V DC.
  • Contact Configuration: Fixed four-pole with front terminals.
  • Rated Insulation Voltage (Uᵢ): 1000 V.
  • Rated Impulse Withstand Voltage (Uᵢₘₚ): 8 kV.
  • Short-Circuit Breaking Capacity (I_cₛ): Up to 65 kA AC depending on voltage; 36 kA DC with poles in series.
  • Terminal Type and Size: Bolt terminals, front connection; busbar 85–200 mm².
  • Mechanical Durability: 25,000 operations.
  • Electrical Durability: 8,000 operations at 120 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT4N 160?
The rated current (Iₙ) is 125 A, with a setting range from 87.5 to 125 A.
What is the maximum short-circuit breaking capacity?
The short-circuit breaking capacity is up to 65 kA AC depending on voltage and 36 kA DC with poles in series.
What type of terminals does this circuit breaker have?
This circuit breaker features bolt terminals with front connection, suitable for busbars sized 85–200 mm².
What is the rated insulation voltage?
The rated insulation voltage (Uᵢ) is 1000 V.
How many operations can this circuit breaker endure?
It has a mechanical durability of 25,000 operations and an electrical durability of 8,000 operations at 120 cycles/hour.
Is this circuit breaker suitable for both AC and DC applications?
Yes, it is rated for 690 V AC and 750 V DC applications.
What standards does this product conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA068102R1
Barcode 8015644695880
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 125A
Alternative Product SKU XT4N 160 TMA 125-1250 4p F F InN=50%
Write Your Own Review
You're reviewing:ABB XT4N 160 4 pole Normal MCCB Adjustable Thermal-Magnetic Release In=125A Ii=1250A