ABB XT2S 160 3 pole Standard MCCB Adjustable Magnetic Release In=100A Im=600 - 1400A

MPN: 1SDA067769R1

Alt. SKU: XT2S 160 MA 100 Im=600...1400 3p F F

Special Price £372.05 £310.04 Regular Price £572.39

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067769R1]

The TMAX XT2S 160 fixed three-pole circuit breaker features front terminals for straightforward installation and a magnetic release mechanism. It is rated for a continuous current (Iu) of 100 A, with adjustable short-circuit protection (I3) ranging from 600 A to 1400 A, ensuring reliable performance in demanding electrical distribution applications.

Technical Specification

  • Function: Moulded case circuit breaker, 3-pole fixed with magnetic release.
  • Rated Current (In): 100 A.
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics): Up to 85 kA (220-240 V AC), 50 kA (380-440 V AC), 12 kA (690 V AC), 50 kA (250/500 V DC).
  • Connecting Capacity: Busbar 32.5 to 100 mm².
  • Terminal Type: Front bolt terminals, recommended tightening torque 6 N·m.
  • Mechanical Durability: 25,000 cycles.
  • Electrical Durability: 8,000 cycles at 120 operations per hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMAX XT2S 160?
The rated current (I n) is 100 A.
What is the maximum short-circuit breaking capacity?
The short-circuit breaking capacity is up to 85 kA at 220-240 V AC.
What type of terminals does this circuit breaker have?
This circuit breaker features front bolt terminals.
What is the recommended tightening torque for the terminals?
The recommended tightening torque is 6 N·m.
What is the mechanical durability of the circuit breaker?
The mechanical durability is rated for 25,000 cycles.
What is the rated operational voltage for this circuit breaker?
The rated operational voltage is 690 V AC / 500 V DC.
What are the connecting capacity specifications?
The connecting capacity for busbars is from 32.5 to 100 mm².
More Information
Manufacturer Part Number 1SDA067769R1
Barcode 8015644016654
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 100A
Alternative Product SKU XT2S 160 MA 100 Im=600...1400 3p F F
Write Your Own Review
You're reviewing:ABB XT2S 160 3 pole Standard MCCB Adjustable Magnetic Release In=100A Im=600 - 1400A