ABB XT2S 160 3 pole Standard MCCB Adjustable Thermal/Fixed Magnetic Release In=125A Ii=375A

MPN: 1SDA067747R1

Alt. SKU: XT2S 160 TMG 125-375 3p F F

Special Price £599.21 £499.34 Regular Price £921.85

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067747R1]

The C.BREAKER TMGX XT2S 160 is a fixed three-pole circuit breaker featuring front-access terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release (TMG R) with adjustable current ratings from 125 to 375 A, providing reliable protection against overloads and short circuits. Designed for compatibility with standard distribution panels, this breaker ensures consistent performance and durability in industrial and commercial electrical systems.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release.
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Rated Current: 125 A (setting range 87.5–125 A), uninterrupted current 160 A.
  • Short-Circuit Breaking Capacity: Up to 85 kA AC (220-240 V) and 50 kA DC (up to 500 V with poles in series).
  • Insulation Voltage: 1000 V.
  • Impulse Withstand Voltage: 8 kV.
  • Poles: 3 poles (3P).
  • Terminal Connection: Front bolt terminals, torque 6 N·m, suitable for busbars 32.5–100 mm².
  • Mechanical Durability: 25,000 operations (240 cycles/hour).
  • Standards Compliance: IEC 60947-2.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMGX XT2S 160?
The rated current is 125 A, with a setting range of 87.5–125 A and an uninterrupted current of 160 A.
What is the short-circuit breaking capacity of this circuit breaker?
The short-circuit breaking capacity is up to 85 kA AC (220-240 V) and 50 kA DC (up to 500 V with poles in series).
What type of terminals does the C.BREAKER TMGX XT2S 160 have?
It features front bolt terminals with a torque of 6 N·m, suitable for busbars ranging from 32.5 to 100 mm².
What is the insulation voltage of this circuit breaker?
The insulation voltage is 1000 V.
How many poles does the C.BREAKER TMGX XT2S 160 have?
This circuit breaker has 3 poles (3P).
What is the mechanical durability of the circuit breaker?
The mechanical durability is rated for 25,000 operations at a rate of 240 cycles per hour.
What standards does the C.BREAKER TMGX XT2S 160 comply with?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067747R1
Barcode 8015644016432
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 125A
Alternative Product SKU XT2S 160 TMG 125-375 3p F F