ABB XT2S 160 3 pole Standard MCCB Adjustable Thermal/Fixed Magnetic Release In=50A Ii=200A
MPN: 1SDA067743R1
Alt. SKU: XT2S 160 TMG 50-200 3p F F
Why Choose the Moulded Case Circuit Breaker [1SDA067743R1]
The C.BREAKER TMGX XT2S 160 is a fixed three-pole circuit breaker featuring front-facing terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release mechanism (TMG R) with an adjustable current rating range of 50 to 200 A, providing reliable protection against overloads and short circuits. Designed for compatibility with standard distribution boards, this breaker ensures dependable performance in commercial and industrial electrical installations.
Technical Specification
- Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release (TMG R).
- Rated Current: 50 A (setting range 35–50 A), rated uninterrupted current 160 A.
- Rated Operational Voltage: 690 V AC / 500 V DC.
- Short-Circuit Breaking Capacity: Up to 85 kA at 220–240 V AC, 50 kA at 380–440 V AC, 36 kA at 500 V AC, 50 kA at 250 V DC (2 poles in series), 50 kA at 500 V DC (3 poles in series).
- Insulation and Impulse Withstand Voltage: Rated insulation voltage 1000 V, impulse withstand voltage 8 kV.
- Contact Configuration: 3 poles, front terminals with bolt connection (M6 screws), suitable for busbars 32.5–100 mm².
- Mechanical and Electrical Durability: 25,000 mechanical cycles; 8,000 electrical cycles at 120 cycles/hour.
- Power Loss per Pole: 4.09 W at rated operating conditions.
- Tightening Torque: 6 N·m for terminal connections.
Trusted By Customers Worldwide
"Specified by UK panel builders for dependable control." Controls Engineer, UK
Frequently Asked Questions
What is the rated current of the C.BREAKER TMGX XT2S 160?
What is the short-circuit breaking capacity of this circuit breaker?
What is the rated operational voltage for the C.BREAKER TMGX XT2S 160?
What type of terminals does this circuit breaker have?
What is the mechanical and electrical durability of this product?
What is the tightening torque for terminal connections?
What standards and approvals does this product conform to?
| Manufacturer Part Number | 1SDA067743R1 |
|---|---|
| Barcode | 8015644016395 |
| HS Code | 85362090 |
| Country of Manufacture | Italy |
| Manufacturer | ABB |
| Number of Poles | 3 Pole |
| Amperage | 50A |
| Alternative Product SKU | XT2S 160 TMG 50-200 3p F F |