ABB XT2N 160 4 pole Normal MCCB Adjustable Thermal/Fixed Magnetic Release In=25A Ii=160A

MPN: 1SDA067729R1

Alt. SKU: XT2N 160 TMG 25-160 4p F F

Special Price £352.80 £294.00 Regular Price £542.76

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067729R1]

The TMAX XT2N 160 fixed four-pole circuit breaker features front terminals for straightforward installation and maintenance. Equipped with a thermomagnetic release (TMG R) adjustable from 25 to 160 A, it provides reliable overcurrent protection suitable for a range of industrial and commercial applications. Designed for compatibility with standard switchgear systems, this breaker ensures precise tripping performance and long-term operational stability.

Technical Specification

  • Function: Fixed four-pole moulded case circuit breaker with thermomagnetic release.
  • Rated Current: 25 A (setting range 17.5–25 A).
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Number of Poles: 4 poles.
  • Insulation Voltage (Ui): 1000 V.
  • Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics & Icu): Up to 65 kA at 220–240 V AC, 36 kA at 380–440 V AC, 30 kA at 500 V AC, 20 kA at 525 V AC, 10 kA at 690 V AC; 36 kA at 250 V DC (2 poles in series), 36 kA at 500 V DC (3 poles in series).
  • Terminal Type and Connection: Front terminals, bolt type for busbar 32.5–100 mm².
  • Mechanical Durability: 25,000 cycles.
  • Standards Compliance: IEC 60947-2.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the TMAX XT2N 160 circuit breaker?
The rated current is 25 A, with a setting range of 17.5–25 A.
What is the maximum operational voltage for this circuit breaker?
The rated operational voltage is 690 V AC and 500 V DC.
How many poles does the TMAX XT2N 160 circuit breaker have?
This circuit breaker has 4 poles.
What is the short-circuit breaking capacity of this circuit breaker?
The short-circuit breaking capacity varies: up to 65 kA at 220–240 V AC, 36 kA at 380–440 V AC, and 36 kA at 250 V DC (2 poles in series).
What type of terminals does the TMAX XT2N 160 have?
The circuit breaker features front terminals with a bolt type connection for busbars of 32.5–100 mm².
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 25,000 cycles.
What standards does the TMAX XT2N 160 comply with?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067729R1
Barcode 8015644016258
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 25A
Alternative Product SKU XT2N 160 TMG 25-160 4p F F