Do you need some help?

Call us now on: 01706 242050

ABB XT2N 160 3 pole Normal MCCB Adjustable Thermal/Fixed Magnetic Release In=40A Ii=200A

MPN: 1SDA067720R1

Alt. SKU: XT2N 160 TMG 40-200 3p F F

Special Price £263.88 £219.90 Regular Price £405.96

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067720R1]

The TMGX XT2N 160 fixed three-pole circuit breaker features front-access terminals and a thermomagnetic release mechanism, rated from 40 to 200 amps. Designed for reliable protection in industrial and commercial electrical installations, it ensures precise overload and short-circuit response. Its robust construction and compatibility with standard panel mounting make it suitable for a wide range of applications requiring dependable circuit interruption.

Technical Specification

  • Type: Fixed three-pole moulded case circuit breaker with thermomagnetic release TMG R.
  • Rated Current: 40 A (setting range 28...40 A), rated uninterrupted current 160 A.
  • Rated Operational Voltage: 690 V AC / 500 V DC.
  • Short-Circuit Breaking Capacity: Up to 65 kA AC (220-240 V), 36 kA (380-440 V AC), 36 kA DC (250-500 V with poles in series).
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Contact Configuration: 3 poles, front terminal connection with bolt type.
  • Connecting Capacity Main Circuit: Busbar 32.5 to 100 mm².
  • Mechanical Durability: 25,000 cycles at 240 cycles/hour.
  • Tightening Torque: 6 N·m for terminal bolts.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the C.BREAKER TMGX XT2N?
The rated current is 40 A, with a setting range of 28 to 40 A.
What is the short-circuit breaking capacity of this circuit breaker?
The short-circuit breaking capacity is up to 65 kA AC (220-240 V) and 36 kA AC (380-440 V), as well as 36 kA DC (250-500 V with poles in series).
What is the rated operational voltage for the TMGX XT2N?
The rated operational voltage is 690 V AC and 500 V DC.
What is the mechanical durability of this circuit breaker?
The mechanical durability is rated for 25,000 cycles at 240 cycles per hour.
What is the tightening torque required for the terminal bolts?
The tightening torque for the terminal bolts is 6 N·m.
What is the connecting capacity for the main circuit?
The connecting capacity for the main circuit is for busbars ranging from 32.5 to 100 mm².
What standards and approvals does the TMGX XT2N conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067720R1
Barcode 8015644016166
Manufacturer ABB
Number of Poles 3 Pole
Amperage 40A
Alternative Product SKU XT2N 160 TMG 40-200 3p F F
Product Lead Time Please contact us for a delivery time
Write Your Own Review
You're reviewing:ABB XT2N 160 3 pole Normal MCCB Adjustable Thermal/Fixed Magnetic Release In=40A Ii=200A