Do you need some help?

Call us now on: 01706 242050

ABB XT2S 160 4 pole Standard MCCB Fixed Thermal/Adjustable Magnetic Release In=1.6A Ii=16A

MPN: 1SDA067561R1

Alt. SKU: XT2S 160 TMD 1,6-16 4p F F

Special Price £454.15 £378.46 Regular Price £698.70

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067561R1]

The TMAX XT2S 160 fixed four-pole circuit breaker features front-facing terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release (TMD R) adjustable from 1.6 to 16 A, providing reliable protection against overloads and short circuits. Designed for robust performance and compatibility within low-voltage distribution systems, this breaker ensures precise current interruption and long-term operational stability.

Technical Specification

  • Function: Thermomagnetic moulded case circuit breaker with four poles and fixed front terminals.
  • Rated Voltage (Ur): 690 V AC / 500 V DC.
  • Rated Current (In): 1.6 A (setting range 1.12–1.6 A).
  • Number of Poles: 4P (four poles).
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Short-Circuit Breaking Capacity (Ics): Up to 85 kA at 230 V AC; up to 50 kA at 415 V AC; 50 kA DC with pole series connection.
  • Terminal Type: Bolt, front connection, busbar capacity 32.5–100 mm².
  • Mechanical Durability: 25,000 operations.
  • Tightening Torque: 6 N·m recommended for main circuit terminals.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the function of the C.BREAKER TMAX XT2S 160?
It is a thermomagnetic moulded case circuit breaker designed for protection against overloads and short circuits.
What is the rated current range for this circuit breaker?
The rated current is 1.6 A, with a setting range of 1.12–1.6 A.
What is the maximum short-circuit breaking capacity?
It can handle up to 85 kA at 230 V AC, 50 kA at 415 V AC, and 50 kA DC with pole series connection.
What type of terminals does this circuit breaker have?
It features bolt-type front terminals with a busbar capacity of 32.5–100 mm².
What is the mechanical durability of the C.BREAKER TMAX XT2S 160?
The mechanical durability is rated for 25,000 operations.
What is the recommended tightening torque for the main circuit terminals?
The recommended tightening torque is 6 N·m.
What standards does this circuit breaker conform to?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067561R1
Barcode 8015644014575
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 4 Pole
Amperage 1.6A
Alternative Product SKU XT2S 160 TMD 1,6-16 4p F F
Write Your Own Review
You're reviewing:ABB XT2S 160 4 pole Standard MCCB Fixed Thermal/Adjustable Magnetic Release In=1.6A Ii=16A