ABB XT2S 160 3 pole Standard MCCB Adjustable Thermal-Magnetic Release In=80A Ii=800A

MPN: 1SDA067557R1

Alt. SKU: XT2S 160 TMA 80-800 3p F F

Special Price £325.03 £270.86 Regular Price £500.04

Please contact us for a delivery time
Call us now on 01706 242050

Need It Today?

Speak To Our Team

Speak to our experienced team to discuss options for getting your order to you today.

or

Call us now on: 01706 242050
  • Please ensure the items you would like are in stock
  • Please speak to our team before placing an order
  • Additional charges will apply
  • We cannot guarantee the availability of a courier

Found It Cheaper?

Please complete the form below or call us now on 01706 242050

Free delivery on orders over £200

Why Choose the Moulded Case Circuit Breaker [1SDA067557R1]

The C.BREAKER TMAX XT2S 160 is a fixed three-pole circuit breaker featuring front terminals for straightforward installation and maintenance. It incorporates a thermomagnetic release TMA R 80, providing reliable protection with adjustable current settings ranging from 400 to 800 A. Designed for robust performance, this breaker ensures precise overload and short-circuit protection, making it suitable for a wide range of industrial and commercial electrical distribution applications.

Technical Specification

  • Function: Fixed three-pole moulded case circuit breaker with thermomagnetic release TMA R 80.
  • Rated Operational Voltage: 690 V AC, 500 V DC.
  • Rated Current (In): 80 A with setting range 56...80 A.
  • Short-Circuit Breaking Capacity (Ics/Icu): Up to 85 kA at 220-240 V AC, 50 kA at 380-440 V AC, 12 kA at 690 V AC, 50 kA at 250-500 V DC.
  • Number of Poles: 3 poles (3P).
  • Rated Insulation Voltage (Ui): 1000 V.
  • Rated Impulse Withstand Voltage (Uimp): 8 kV.
  • Terminal Connection Type: Front terminals with M6 bolts, tightening torque 6 N·m.
  • Connecting Capacity Main Circuit: Busbar 32.5 to 100 mm².
  • Mechanical and Electrical Durability: 25,000 mechanical cycles, 8,000 electrical cycles at 120 cycles/hour.

Trusted By Customers Worldwide

"Specified by UK panel builders for dependable control." Controls Engineer, UK

Frequently Asked Questions

What is the rated current of the TMAX XT2S 160 circuit breaker?
The rated current (In) is 80 A with a setting range of 56...80 A.
What is the short-circuit breaking capacity of this circuit breaker?
It has a short-circuit breaking capacity of up to 85 kA at 220-240 V AC, 50 kA at 380-440 V AC, 12 kA at 690 V AC, and 50 kA at 250-500 V DC.
What type of terminals does the TMAX XT2S 160 have?
The circuit breaker features front terminals with M6 bolts.
What is the tightening torque for the terminal connections?
The tightening torque for the terminal connections is 6 N·m.
What is the mechanical and electrical durability of this circuit breaker?
It has a mechanical durability of 25,000 cycles and an electrical durability of 8,000 cycles at 120 cycles/hour.
What is the rated insulation voltage of the TMAX XT2S 160?
The rated insulation voltage (Ui) is 1000 V.
Is there any conformity information available for this product?
See the manufacturer's data sheet for standards and approvals.
More Information
Manufacturer Part Number 1SDA067557R1
Barcode 8015644014537
HS Code 85362090
Country of Manufacture Italy
Manufacturer ABB
Number of Poles 3 Pole
Amperage 80A
Alternative Product SKU XT2S 160 TMA 80-800 3p F F